Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/16/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 02/14/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* STORE: 1) BOXES MORE THAN 1/4" BOX TO SURFACE OR FLUSH COMBUSTIBLES 314.20 2) PROTECT CONDUCTORS FROM SHARP METAL EDGES AT CUT HOLES 3) PLEASE VERIFY SEALING OF RACEWAYS PER 300.7 WALK IN BOXES 4) FINISH ROOF 5) PARTIAL INSPECTION SIGNS AND NEON: 1) PLEASE PROVIDE INSTRUCTIONS FOR STRIP LEDS 2) BOX OVERFILLED (DOG HOUSE) 3) NEED SWITCH AND LOCK OUT NEON |