Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2011 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 02/10/2011 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* | |
| 01/26/2011 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL DEVICES 8' AND BELOW TO BE PLUGED, SWITCHER OR PLASTED FOR POWER 2) FINISH PANELS AND CLEAN EXCESS FOREIGN MATERIAL AND DIRT FROM PANELS 3) USE APPROVED BELL END OR BUSHINGS 352.46, 300.4 & 110.3 4) NEED LETTER OF TORQUE FOR EQUIPMENT 5) CABLE BRACING NEEDED PER MANUFACTURES INSTRUCTIONS 6) SUPPORT PVC CONDUT ABOVE SES 7) PLANS CALL FOR 4 SETS OF 400 MIMILL-WE HAVE ONLY 3 SETS 400 RECALL 8) OK CONNECTIONS TO GRILLS |
|
| 01/21/2011 | ELECTRIC - TEMPORARY SERVICE | Cancelled | IVRS - RI canceled |