Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM02006
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/05/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection 1) MAIN BREAKER TO BE INSTALLED AT TOP OF BUSS PER LISTING OF PANEL, SEE INSTRUCTIONS INSIDE DOOR 2) NOTE: #2 LAST INSPECTION WILL APPLY, PAY REINSPECTION FEE AT 201 N. STONE PRIOR TO NEXT INSPECTION 3) NOTE: MAIN BREAKER WAS RELOCATED TO BOTTOM OF BUSS ?? |
|
| 09/30/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/24/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MINIMUM WIRE SIZE ON LINE TAPS 1/0 PER LISTING-SEE INSTRUCTION/INFO SHEET ON BACK COVER 2) NO COMPLIANCE WITH NOTE #2 9/14/10 3) A REINSPECTION FEE WILL BE ASSESED NEX INSPECTION IF NO COMPLIANCE 4) SERVICE ENERGIZED PRIOR TO INSPECTORS APPROVAL |
|
| 09/14/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 3/4 PIPE ON TOP OF PANEL CONNECTOR LOOSE AND NO STRAPPING 2) #1 STILL HAS TO BE EXPLAINED MAIN DISCONNECT MISSING HOLDOWN SCREW |
|
| 08/26/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |