Permit: T10CM02006

Parcel: 12511434A


Addresses:

3644 E 4TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM02006

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/14/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/05/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
1) MAIN BREAKER TO BE INSTALLED AT TOP OF BUSS PER LISTING OF PANEL, SEE INSTRUCTIONS INSIDE DOOR
2) NOTE: #2 LAST INSPECTION WILL APPLY, PAY REINSPECTION FEE AT 201 N. STONE PRIOR TO NEXT INSPECTION
3) NOTE: MAIN BREAKER WAS RELOCATED TO BOTTOM OF BUSS ??
09/30/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/24/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MINIMUM WIRE SIZE ON LINE TAPS 1/0 PER LISTING-SEE INSTRUCTION/INFO SHEET ON BACK COVER
2) NO COMPLIANCE WITH NOTE #2 9/14/10
3) A REINSPECTION FEE WILL BE ASSESED NEX INSPECTION IF NO COMPLIANCE
4) SERVICE ENERGIZED PRIOR TO INSPECTORS APPROVAL
09/14/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 3/4 PIPE ON TOP OF PANEL CONNECTOR LOOSE AND NO STRAPPING
2) #1 STILL HAS TO BE EXPLAINED MAIN DISCONNECT MISSING HOLDOWN SCREW
08/26/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*