Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM01990
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/20/2011 | ELECTRIC - FINAL | Approved | ||
06/13/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DISTRIBUTION BLOCKS ARE ONLY COMPONENT MARKED NOT LISTED 2) ONLY ONE CONDUCTOR PER LUG 3) CANNOT PARALLEL CONDUCTORS SMALLER THAN 1/0 4) TIGHTEN LOOSE FITTINGS 5) LOOSE "B" PHASE LUG 6) SECURE CONTROL TOWER TO FLOOR 7) PLEASE VERIFY LISTING FOR WASTE EDGE CONTROL CABINET 8) NEED APPROVED ELECTRICAL PLANS ON SITE-MORE THAN 1-LINE 9) NO RISER INSTALLED |