Permit: T10CM01977

Parcel: 132162990


Addresses:

1462 E EL ATAJO

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/16/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TRAP ON FAN COIL IS FLATTENED AT BOTTOM
2) REPLACE TRAP
3) PROVIDE AN OVERFLOW SENSOR
4) CONNECT OVERFLOW SENSOR ON PUMP
5) USE PURPLE PRIMER ON ALL FITTINGS
6) PROVIDE A COVER PLATE ON ELECTRIC BOX IN CLOSET
7) MARK DATA PLATE WITH PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY
8) ID FUSE BANKS IN DISCONNECT
9) REMOVE ALL EXTERNAL INSULATION EXPOSED ON ROOF TOP DUCTING
10) PROVIDE MININUM R8 DUCT LINER
11) TERMINATE PUMP DRAIN INTO PVC ON ROOF WITH A FITTING
12) TERMINATE PVC WITH AN ELBOW AND NIPPLE
13) PAINT EXPOSED PVC WITH LATEX PAINT AND USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE INSIDE AND OUTSIDE THE HOUSE
14) PROVIDE THE REQUIRED DRAWING FOR A NEW ROOF TOP INSTALLATION