Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM01944
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/17/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH CHICO POURS |
|
11/15/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO POUR SEALS 2) ROOF OK 3) FINISH PREVIOUS ITEMS 4) SEAL OFF TO BE ACCESSIBLE |
|
11/14/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEPERATE CONDUCTORS IN SEALS 2) FILL SEALS TO CORRECT AMOUNTS 3) SEAL UNUSED SEALS 4) SEAL ? ROOT PUMPS AS PER MANUFACTURES INSTRUCTIONS 5) SEAL RACEWAYS TO LIGHTS AND SIGNS PER 514.8 6) CLEAN SURFACE UNDER GROUND BAR 250.12 AND 250.8 NO SHEET METAL THREAD SCREWS |
|
11/07/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) EPO PROVIDED IS PER PLAN-NOTE POSSIBLE VANDALISM COULD OCCUR AND CREATE A NON CODE COMPLIANT SITUATION |