Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM01943
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/18/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PROTECT SEAL TITE FROM SHARP METAL EDGES 2) CREAMER ONLY EQUIPMENT N EED VERIFICATION |
|
11/17/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) USE CORRECT SIZED WIRE CONNECTORS AT POLE LIGHTS 2) FINISH SEALING COOLERS AS DISCUSSED 3) FINISH PREVIOUS INSPECTION ITEMS 4) ROOF LADDER NOT SECURED |
|
11/15/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) FINISH PREVIOUS |
|
11/14/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOXES MORE THAN 1/4" 314.20 2) PROTECT CONDUCTORS 300.4 3) LABEL DISCONNECTS 4) REMOVE BOND JUMPER AT MAIN PANEL 5) WORKING CLEARANCES AT DISCONNECTS 6) SEAL WALK IN BOX 300.7 7) VERIFY LISTING OF EQUIPMENT |