Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T10CM01943
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/02/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK ELECTRIC ABOVE CEILING |
|
11/01/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH PREVIOUS ITEMS 2) BOXES OVER FILLED |
|
10/27/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) WHAT ARE M/C COILS ABOVE CEILING AND UPPORT 2) SECURE PVC ABOVE CEILING 3) FINISH SIGN RACEWAYS 4) VERIFY DERATING OF CONDUCTORS 310.15 5) RECEIVED LETTER OF TORQUE |
|
10/26/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
10/25/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK LIGHTS IN GRID 2) OK SERVICE TO MAIN IN SWITCHBOARD 3) NEED LETTER OF TORQUE FOR SWITCHBOARD 4) FINISH VDV CABLING 5) FINISH POWER DROPS 6) 8' AND DOWN TO BE PLUG PLATED AND READY FOR TESTING |
|
10/24/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) WILL NEED TO POST BOND FOR POWER 2) FINISH VDV CABLING |
|
09/26/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |