Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/12/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CHEMICAL ADDITION IS ADDED PLEASE PROVIDE LISTING SHEET FOR ASSE 1055 B DEVICE TO VERIFY CORRECT TYPE OF BACKFLOW PROTECTION FOR POTABLE WATER |
|
| 05/06/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE GRAVITY DRAIN TO DAYLIGHT FOR WATER HEATER T & P 2) PROVIDE LUG COVER IN WATER HEATER DISCONNECT 3) PROVIDE 1" MINIMUM AIR GAP AT DRAIN TERMINATIONS THAT ARE INDIRECT DRAINS 4) PROVIDE FULL SIZE 2" CLEANOUT FOR 3 COMP SINK 5) SECURE THE ROOF FLASHING AND MAKE IT WEATHER TIGHT 6) FIX LEAKS AT P-TRAPS 7) PROVIDE WATER HEATER ARRESTORS AT WASHER WATER CONNECTIONS |