Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/16/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
05/12/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CHEMICAL ADDITION IS ADDED PLEASE PROVIDE LISTING SHEET FOR ASSE 1055 B DEVICE TO VERIFY CORRECT TYPE OF BACKFLOW PROTECTION FOR POTABLE WATER
05/06/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE GRAVITY DRAIN TO DAYLIGHT FOR WATER HEATER T & P
2) PROVIDE LUG COVER IN WATER HEATER DISCONNECT
3) PROVIDE 1" MINIMUM AIR GAP AT DRAIN TERMINATIONS THAT ARE INDIRECT DRAINS
4) PROVIDE FULL SIZE 2" CLEANOUT FOR 3 COMP SINK
5) SECURE THE ROOF FLASHING AND MAKE IT WEATHER TIGHT
6) FIX LEAKS AT P-TRAPS
7) PROVIDE WATER HEATER ARRESTORS AT WASHER WATER CONNECTIONS