Permit: T10CM01942

Parcel: 128050130


Addresses:

655 S CRAYCROFT RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/22/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
04/19/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/01/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO COVER ROUGH & INTERMEDIATE PLUMBING FOR WASHER AND P-4 ONLY
03/28/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 3/4" HOT AND COLD TO WATER HEATER AREA OK
2) UNDERGROUND DRAINAGE FOR WASHER AND P-4 SINK
3) DWV TEST THRU ROOF OK
4) PROVIDE APPROVED SUPPORT FOR VENT THRU ROOF AT OFF SET
5) PROVIDE PIPE PROTECTION PLATES FOR INWALL COPPER WITHIN 1 1/2" OF STUD FACE. AT WASHER AND P-4 SINK AREA
6) PLAN SPECS INTERCEPTOR WITH INTEGRAL FLOW CONTROL INSTALL PER APPROVED PLAN ON YOUR 3 COMP SINK. VENT IS INCORRECT INTERCEPTOR, NEEDS TO BE 2" FOR 2" OUTLET PIPING. WHERE IS FLOOR SINK ?
7) PLEASE LEAVE A CONTACT PHONE NUMBER SO THAT YOUR PLUMBER CAN BE ON SITE FOR NEXT INSPECTION