Permit: T10CM01933

Parcel: 119180800


Addresses:

3640 S 16TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM01933

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) RECEIVED LETTER FOR DELETION OF OUTLETS
2) FRYS HAS BEEN NOTIFIED ABOUT EXISTING ON SAFE CONDITIONS
12/20/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
12/17/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED LETTER FROM ARCH OR ENGINEER FOR DELETED RECEPTS
2) FINISH #2,3,4 & 5
12/15/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) GROUND FLOOR BOXES SCREWS FOR PLATE BOND AND MISSING WATER EXTRUSTION GASKET
2) FIXTURES FOR VALANCES 410.73 (G)
3) CORDS NOT ALLOWED ABOVE CEILING 410.7 & 8-PHARMACY
4) OLD EXISTING ELECTRICAL LAYING ON GRID IN AN UNSAFE CONDITION
5) VERIFY RECEPTS PHARMACY AREA AS MARKED
12/14/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
12/13/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OLD BOXES LEFT OPEN-FILL UNUSED OPENINGS IN BOXES
2) REMOVE ABANDONED M/C CABLE
3) SUPPORT M/C FOR CORD DROPS