Permit: T10CM01933

Parcel: 119180800


Addresses:

3640 S 16TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM01933

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/03/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FILL UNUSED OPENING IN RACK CONTROL CABINETS
2) CORRECT GROUNDING FOR EFFECTIVE GROUND PATH
3) OK CASES ELECTRIC AFTER CORRECTIONS
4) OK PREVIOUS ITEMS
12/01/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT STACK LUGS, DO NOT INSTALL ON ISOLATION STRIP
2) NEED BOND OF FLEX RACEWAYS
3) GROUNDING ELECTRODE AND GROUNDED BOND JUMPER TO USE SAME LUG
4) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANELS
5) FINISH #3 & 5 FROM PREVIOUS INSPECTION
6) SUPPORT RACEWAYS ABOVE PANEL "PB3"
7) USE APPROVED HARDWARE TO HANG PANEL NOT DRYWALL SCREWS
8) PROVIDE PHYSICAL PROTECTION $8 GEC TO TRANSFORMERS
11/23/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 2 FLOOR BOXES AND PVC CONDUIT FOR GONDULAS BETWEEN 13 & 14
11/09/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CLEARANCE FOR OTHER EQUIPMENT NOT MORE THAN 6"
2) TIGHTEN LOOSE FITTINGS
3) LABEL EQUIPMENT
4) CLEAN SURFACE UNDER GROUND BAR 250.12
5) MAINTAIN WORKING CLEARANCE BACK PANELS
6) NEED ELECTRICIANS PRESENT TO OPEN EQUIPMENT
7) DO NOT ENERGIZE WITHOUT CLEARANCES