Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM01933
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/03/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FILL UNUSED OPENING IN RACK CONTROL CABINETS 2) CORRECT GROUNDING FOR EFFECTIVE GROUND PATH 3) OK CASES ELECTRIC AFTER CORRECTIONS 4) OK PREVIOUS ITEMS |
|
12/01/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT STACK LUGS, DO NOT INSTALL ON ISOLATION STRIP 2) NEED BOND OF FLEX RACEWAYS 3) GROUNDING ELECTRODE AND GROUNDED BOND JUMPER TO USE SAME LUG 4) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANELS 5) FINISH #3 & 5 FROM PREVIOUS INSPECTION 6) SUPPORT RACEWAYS ABOVE PANEL "PB3" 7) USE APPROVED HARDWARE TO HANG PANEL NOT DRYWALL SCREWS 8) PROVIDE PHYSICAL PROTECTION $8 GEC TO TRANSFORMERS |
|
11/23/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 2 FLOOR BOXES AND PVC CONDUIT FOR GONDULAS BETWEEN 13 & 14 |
|
11/09/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CLEARANCE FOR OTHER EQUIPMENT NOT MORE THAN 6" 2) TIGHTEN LOOSE FITTINGS 3) LABEL EQUIPMENT 4) CLEAN SURFACE UNDER GROUND BAR 250.12 5) MAINTAIN WORKING CLEARANCE BACK PANELS 6) NEED ELECTRICIANS PRESENT TO OPEN EQUIPMENT 7) DO NOT ENERGIZE WITHOUT CLEARANCES |