Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) COURTESY UNSCHEDULED INSPECTION FOR DERIC |
|
| 09/10/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAKE ENCLOSURE WEATHER TIGHT 2) INSULATION SHALL BE INSTALLED IN A WORKMANSHIP LIKE MANNER IN ACCORDANCE WITH MANUFACTURES INSTRUCTIONS 3) PROVIDE AN APPROVED B-VENT SUPPORT 4) PROVIDE CLAMPS THAT WILL SECURE PIPING TO SUPPORTS WITHOUT DAMAGING INSULATION 5) INSTALL FLASHINGS WITH ROOF SEAPANT, NOT SILICONE 6) PROTECT ROOF FROM SHARP EDGES OF UNISTRUT 7) CONTINUED DENIED INSPECTIONS MAY RESULT IN REFEES TO CONTRACTOR |
|
| 08/20/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) VENT FROM WATER HEATER TO TRAVEL MINIMUM 5' VERTICAL BE DBL WALL LEAVING ENCLOSURE AND HAVE MINIMUM 1" CLEARANCE FROM COMBUSTIBLES WITH APPROVED VENT CAP 2) POTABLE WATER PIPING SUBJECT TO FREEZING TO BE PROPERLY INSULATED 3) PROVIDE CORRECT COMBUSTION AIR IN UPPER 12" OF ENCLOSURE FOR 40,000 BTU APPLIANCE 4) PROVIDE APPROVED BASE WITH WEATHER PROOF ENCLOSURE FOR STORAGE TANK AND PUMP ASSEMBLY 5) SECURE ALL SOLAR LOOP PIPING AT CORRECT INTERVALS 6) J-HOOK INTO ROOF REQUIRE REMOVAL AND REPAIR TO ROOFING SURFACE WITH APPROVED ROOFING PRODUCTS |