Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/28/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STORAGE TANK CNNOT BE SET OVER A FLOOR DRAIN-ACCESS FOR CLEANING AND SERVICE IS REQUIRED AT FLOOR DRAIN 2) PROVIDE LISTING FOR PAD FOR STORAGE TANK, PAD SHOULD NOT BE ALTERED CUT OR DRILLED 3) MAKE UP VENT CONNECTOR AT SINGLE TO DBL WALL CORRECTLY 4) PIPING TO BE SUPPORTED AT CHANGES OF DIRECTION AND AT CORRECT INTERVALS 5) PROVIDE CORRECT PRESSURE RELIEF DRAIN O APPROVED LOCATION FOR STORAGE TANK 6) PROVIDE COMBUSTION AIR FOR WATER HEATER (GAS) 7) SOLAR LOOP PIPING TO BE PROPERLY SUPPORTED |