Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T10CM01895
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/10/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) SEAL ROOF FLASHINGS WITH TAR, SILICONE IS NOT APPROVED FOR THAT USE |
|
07/21/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #2159 2) SECURE VENT WITH SCREWS AT EACH JOINT 3) FLEX IS NOT ALLOWED ON RELIEF DRAIN 4) SEDIMENT TRAP IS REQUIRED AT GAS CONNECTION 5) A GAS FLEX MAY NOT BE RE-USED 6) ALL TUBING ON ROOF REQUIRES SUPPORTS 7) PATCH NAIL HOLES |