Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/22/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES FROM 7/26/10-PROVIDE AN APPROVED BASE FOR STORAGE TANK. THERE ARE STILL GAPS IN INSULATION FROM HEATER TO STORAGE TANK, SEALL OFF ROOF OF STORAGE TANK, MAKE WEATHER TIGHT AND WEATHR PROOF. WOOD OF STORAGE ENCLOSURE TO NOT BE IN CONTACT WITH GROUND TO PREVENT TERMITES |
|
| 07/26/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | 1) POTABLE COPPER PIPING SHALL NOT BE IN CONTACT WITH GALVANIZED METAL 2) SEAL PIPING INSULATION AT JOINTS, FITTING AND PROTECT FROM SUN EXPOSURE 3) PROVIDE LISTING FOR WATER HEATER BASE 4) SEAL LOOP TUING TO E SUPPORTED UP OFF OF ROOF AT CORRECT INTERVALS, NO J-HOOKS THUR ROOF SURFACE 5) PROVIDE CLAMPS THAT DO NOT CRUSH INSULATION 6) PROVIDE CORRECT BREAKER FOR KCAK ENERGY SAVING DEVICE WITH INSTALLATION INSTRUCTION ON SITE 7) TIGHTEN CONNECTORS FOR CONDUIT |
|
| 07/23/2010 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - RI canceled |