Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/24/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PLUMBING TAPE IS NOT AN APPROVED PIPE SUPPORT AND PROVIDES NO SUPPORT AS INSTALLED 2) SECURE AND SUPPORT T & P DRAIN, CONDENSATE, GAS & WATER WITH APPROVED PIPING SUPPORTS 3) SEAL ALL JOINTS ON INSULATION 4) APPLY RECOMMENDED COATING AND CORRECT LOOSE CLAMPS 5) INSTALL FLASHINGS PROPERLY 6) NOTE: POSSIBLE LEAK AT ROOF PENETRATION |
|
| 08/02/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT ALL PIPING AT GAS WATER HEATER 2) SUPPORT PIPING ON ROOF AT MAX 6" ON CENTER AND PROVIDE CLAMPS THAT SECURE THE PIPING IN PLACE 3) INSULATE ALL EXPOSED PIPING PER MINIMUM STANDARDS ESTABLISHED BY THE MANUFACTURE 4) SEAL ALL JOINTS AND APPLY PROTECTIVE COATING 5) REPAIR ALL NAIL HOLES WITH ROOF PATCHING MATERIAL |
|
| 07/20/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |