Permit: T10CM01890

Parcel: 11942006E

Inspection Status: Approved

Inspection History: MECHANICAL - HYDRONIC PIPING

Date Description Inspector Results Comments
11/09/2011 MECHANICAL - HYDRONIC PIPING Approved IVRS - Inspection :*
11/02/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) HYDRO TEST OF MECHANICAL ROOM PIPING OK, OK TO INSULATE
2) DUCT WORK AND HYDRO PIPING ABOVE T-BAR CEILINGS OK TO COVER
10/27/2011 MECHANICAL - HYDRONIC PIPING Not ready for Inspection IVRS - Inspection :*
10/14/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) HYDRO PIPING TO TV UNITS PRESSURE TEST OK, OK TO COMPLETE INSULATION
10/13/2011 MECHANICAL - HYDRONIC PIPING Not ready for Inspection IVRS - Inspection :*
09/22/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) HYDRO RISER TO BLDG 1 HAS MANUAL BLEED VALVES ABOVE HARD LID WITH NO ACCESS, PROVIDE ACCESS
2) NO OTHER COMPLETED WORK OBSERVED
08/31/2011 MECHANICAL - HYDRONIC PIPING Not ready for Inspection IVRS - Inspection :*
07/19/2011 MECHANICAL - HYDRONIC PIPING Not ready for Inspection IVRS - Inspection :*