Permit: T10CM01888

Parcel: 11942006E

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
07/18/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
07/07/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/06/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/31/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/24/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/19/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) HWS & R AND CHWS & RETURN HYDRO TEST FROM RISERS TO BRANCH RUNS AT T.V. UNITS OK, OK TO INSULATE
2) ROUND DUCT MED. AND LOW PRESS OK TO INSULATE
12/17/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CHW S/R RISERS BETWEEN BLDG 5 AND 4 PRESS TEST OK, OK TO INSULATE FITTINGS
2) HWS/R RISERS BETWEEN BLDG 5 & 6 PRESS TEST OK, OK TO INSULATE, BACKFILL ONLY AFTER PHOTOS OF INSULATED FITTINGS
12/15/2010 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/13/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CWS & R AND HWS & R THRU FOUNDATION AND UP INTO MECHANICAL ROOM BLDG 5 TO BLDG 6 PRESSURE TEST OK, OK TO INSULATE 90 DEGREE ELLS, OK TO BACK FILL WITH PHOTOS OF 90 DEGREES ELLS
2) LOOP BETWEEN BLDG 4 AND BLDG 5 OK ON HWS & R, OK TO INSULATE 90 DEGREES ELLS N.W. ONLY
12/08/2010 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*