Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/27/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) NEED OLD WRITE-UPS ON SITE |
|
| 03/31/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEED LETTER OF TORQUE 2) CONDUITS NOT TO EXTEND INTO SWITCH BOARD MINIMUM 3" 408.5 3) MAINTAIN SAFE WORKING SPACE 110.26 4) NEED ACCESS TO PANELS AND SWITCH BOARD 5) OK CONDUITS RUNS FOR LIGHTING AND A/C STUBS |
|
| 12/28/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH EXTERIOR COLUMNS SOUTH & BROADWAY |
|
| 11/23/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |