Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 07/22/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A TRAP IN CONDENSATE DRAIN LINE 2) CONNECT OVERFLOW SENSOR ON CONDENSATE PUMP 3) PROVIDE THE REQUIRED SEDIMENT TRAP IN GAS LINE TO FURNACE 4) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMA FLEX 5) PROVIDE THE REQUIRED GFI SERVICE RECEPT 6) LOW VOLTAGE WIRE MUST E PROTECTED FROM DAMAGE 7) EXTEND FURNACE VENT MINIMUM 3' ABOVE EVAP COOLER AND PROVIDE AN APPROVED CAP |
|
| 07/20/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |