Permit: T10CM01846

Parcel: 12709011M


Addresses:

335 N WILMOT RD


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T10CM01846

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
09/29/2010 ELECTRIC - UFER Approved IVRS - Inspection :*
09/24/2010 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1) BOND JUMPER ON LINE SIDE 250.102 AND 250.66
2) CONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT
3) OK 2 GROUND ROD AND 3/0 CU
09/22/2010 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*
1) SERVICE DISCONNECT TO HAVE NEUTRAL BAR INSTALLED. NEUTRAL IN DISCONNECT WITH MAIN BONDING JUMPER INSTALLED
2) NEED MINIMUM 2 GROUND RODS UNLESS < 25 OHMS TO EARTH
09/21/2010 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*