Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T10CM01846
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2010 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
09/24/2010 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) BOND JUMPER ON LINE SIDE 250.102 AND 250.66 2) CONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT 3) OK 2 GROUND ROD AND 3/0 CU |
|
09/22/2010 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* 1) SERVICE DISCONNECT TO HAVE NEUTRAL BAR INSTALLED. NEUTRAL IN DISCONNECT WITH MAIN BONDING JUMPER INSTALLED 2) NEED MINIMUM 2 GROUND RODS UNLESS < 25 OHMS TO EARTH |
|
09/21/2010 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* |