Permit: T10CM01810

Parcel: 11706081D


Addresses:

345 E CONGRESS ST


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T10CM01810

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/14/2011 FIRE SPKLR - FINAL Approved
09/27/2011 FIRE SPKLR - FINAL Denied Revisions will be required to the original permit to include details of the mechanical room. These include but are not limited to:
Details for walls ect.
Electrical including pump controls
Heat for pump room per NFPA 20
Drain for the pump room per NFPA 20
Model and serial numbers for jockey and fire pumps
Placement of all piping, valves normally open or closed.
All tampers and flows
Rewire plug for block heater, electrical cord to short.
Need copy of pump test (flows and table)
09/09/2011 FIRE SPKLR - FINAL Denied Need fire pump final and fire alarm final.