Permit: T10CM01810

Parcel: 11706081D


Addresses:

345 E CONGRESS ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM01810

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/25/2011 MECHANICAL - FINAL Approved
09/07/2011 MECHANICAL - FINAL Approved
09/07/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) T-STAT WIRE EXPOSED TO EXTERIOR IS TO BE PROTECTED FROM DAMAGE INCLUDING U.V. RAYS, PROVIDE CONDUIT OR OTHER APPROVED MEANS
2) LINE SET INSULATION TO BE PROTECTED FROM U.V. DAMAGE, DUCT TAPE NOT AN APPROVED MEANS
3) FIRE/SMOKE DAMPER TEST OK
4) NO LIFE SAFETY ISSUES OBSERVED AT THIS TIME, SEE BLDG INSPECTOR FOR TEMP C OFO
09/06/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*