Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM01810
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2011 | ELECTRIC - FINAL | Approved | ||
09/08/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) WIRE FOR FIRE PUMP EQUIPMENT TO BE PER NEC 695.6 (E), (F) AND (G) & 695.12 (C) FROM FPN: NFPA 20 9.7 AND 10.3.3.1 2) PUMP CONTROLLER LISTED 440-480 VAC ANY CHANGES TO HAVE FIELD EVALUATION BY NRTL 3) VERIY BOX FILL 814.16 |
|
09/06/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PANEL DIRECTORIES TO BE PER 408.4 2) VERIFY GUTTER PER 366.22 (A) 3) FILL UNUSED OPENINGS IN PANEL AND BOX COVERS 4) SUPPORT CONDUIT TO FIRE PUMP EQUIPMENT 5) NO POWER TO FIRE PUMP-NOTE: ARTICLE 695 AND ? 20 6) FINISH CAMERAS FOR CABLING AND CONDUIT INSPECTION 7) SPLICES TO BE FOR WET LOCATION 8) OK ELEVATOR MAIN DISCONNECT 9) FINISH ELECTRIC |