Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T10CM01810
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2011 | ELECTRIC - UNDERGROUND | Approved | ||
08/24/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK PVC CONUITS RAILROAD SIDE OK FLOOR 2 & 3 & 4 LIGHTS AFTER CORRECTIONS |
|
08/16/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 3/4" AT PUMP ROOM AREA 2) OPEN 12 FIXTURES TO INSPECT 1ST FLOOR |
|
08/08/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK LAST 15' TO TEP 2) OK LAST 40' TO DATA 3) SPACE FOR BELL ENDS |
|
07/27/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK PRIMARY SERVICE LATERALS 6-5" PVC WITHIN 15' OF TEP 2) OK DATA PRIMARY 3-4" PVC |
|
07/21/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK U.G. POWER AND PHONE SOUTHEAST OF OUTSIDE BLDG |
|
07/20/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK AS MARKED PVC CONDUITS 2) WEST SIDE PVC CONDUITS ARE AT 360 DEGREE IN RUNS-WILL NEED PULL BOXES |
|
07/19/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK AS MARKED PVC CONDUITS 2) NOTE: DEPTHS PER 300.5 |
|
06/15/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) GL: 10. TO ELEVATOR EQUIPMENT ROOM LINE 1 |
|
05/19/2011 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
05/18/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
05/17/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
05/02/2011 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/02/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
04/25/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
04/18/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
04/04/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
03/22/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK TO INCASE ELECTRIC ROOM OUT 40' 6-/3/4" PVC 26-5" PVC AND 2-4" PVC |
|
03/21/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) PVC CONDUITS TO BE PER 300.5 24" OR ENCASED 2" X 2" X 2" X 2" |
|
02/23/2011 | ELECTRIC - UNDERGROUND | Partial Approval | 2 EACH 3/4" PVC AND 2" PVC UNDER RAMP AT ENTRANCE. OK TO COVER | |
02/10/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
02/09/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
01/15/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 1ST FLOOR LIGHTING 3 TO 6.5 AS MARKED 2) RECEIVED CHECK #112962 FOR $165.00 |