Permit: T10CM01810

Parcel: 11706081D


Addresses:

345 E CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T10CM01810

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2011 ELECTRIC - UNDERGROUND Approved
08/24/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :* OK PVC CONUITS RAILROAD SIDE
OK FLOOR 2 & 3 & 4 LIGHTS AFTER CORRECTIONS
08/16/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 3/4" AT PUMP ROOM AREA
2) OPEN 12 FIXTURES TO INSPECT 1ST FLOOR
08/08/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK LAST 15' TO TEP
2) OK LAST 40' TO DATA
3) SPACE FOR BELL ENDS
07/27/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK PRIMARY SERVICE LATERALS 6-5" PVC WITHIN 15' OF TEP
2) OK DATA PRIMARY 3-4" PVC
07/21/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK U.G. POWER AND PHONE SOUTHEAST OF OUTSIDE BLDG
07/20/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK AS MARKED PVC CONDUITS
2) WEST SIDE PVC CONDUITS ARE AT 360 DEGREE IN RUNS-WILL NEED PULL BOXES
07/19/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK AS MARKED PVC CONDUITS
2) NOTE: DEPTHS PER 300.5
06/15/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) GL: 10. TO ELEVATOR EQUIPMENT ROOM LINE 1
05/19/2011 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
05/18/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
05/17/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
05/02/2011 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/02/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
04/25/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
04/18/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
04/04/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
03/22/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK TO INCASE ELECTRIC ROOM OUT 40' 6-/3/4" PVC
26-5" PVC AND 2-4" PVC
03/21/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) PVC CONDUITS TO BE PER 300.5 24" OR ENCASED 2" X 2" X 2" X 2"
02/23/2011 ELECTRIC - UNDERGROUND Partial Approval 2 EACH 3/4" PVC AND 2" PVC UNDER RAMP AT ENTRANCE. OK TO COVER
02/10/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
02/09/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
01/15/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 1ST FLOOR LIGHTING 3 TO 6.5 AS MARKED
2) RECEIVED CHECK #112962 FOR $165.00