Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T10CM01808
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) SUPPLY AND EXHAUST IN RESTROOMS OK 2) CONDENSATE DRAINS OK TO INSULATE |
|
08/02/2010 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE ISOLATORS AT CALLED FOR IN GEN. NOTE 9 AND DETAIL 6-M4 2) PROVIDE PROPER GAP AT FLEX CONNECTORS (METAL EDGES WILL NOT TOUCH EACH OTHER) 3) SEAL CONNECTIONS TO UNITS 4) ALL BRANCH TAPS TO BE CONICAL PER PLANS 5) ALL CONDENSATE PIPING TO BE INSULATED 6) PROVIDE PROPER FALL ON CONDENSATE |