Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/20/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE ITEM #2 FROM PREVIOUS INSPECTION |
|
| 07/30/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING OF PANELS WITH GROUND CLIPS AND WEB LUGS NOT PER MANUFACTURERS INSTRUCTIONS 2) #8 GEC TO BE INSTALLED PER NEC 250.64 (B) 3) GEC TO CONNECT TO EACH INVERTER |