Permit: T10CM01801

Parcel: 11901076A


Addresses:

3346 S 6TH AV #100


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T10CM01801

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
10/27/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) BACTERIA REPORT AND STERILIZATION REPORT ON SITE
2) COMPLETE ITEMS #2, 8, 9 AND 10 FROM 10/21/11
10/21/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) TERMINATE ALL CLEANOUTS CORRECTLY
2) SEAL INSULATION CORRECTLY PER MANUFACTURE
3) PROVIDE MIN SPAN SUPPORT FOR MOP SINK VENT
4) PROVIDE 1" MINIMUM AIR GAPS FOR T & P DRAINS
5) PROVIDE VENTING SYSTEM MEETING INSTALLATION INSTRUCTIONS PAGE 13 WITH CORRECT ASTM NUMBER AND PRIMER THEN GLUE
6) PROVIDE A DRIP PAN FOR ELEVATED WATER HEATER
7) REMOVE THE TEST GAUGE SET UP ON COLD WATER PIPING AT STORAGE TANK AND PROVIDE EXPANSION TANK PER PLAN
8) PIPE THE STORAGE TANK PER APPROVED PLAN
9) PROVIDE TEMPERING FOR PUBLIC USE LAVS
10) ALL FIXTURES TO BE FUNCTIONAL
11) PROVIDE STERILIZATION AND BACTERIA REPORT
12) PROVIDE FACTORY TAPPED CLEANOUT PLUGS AND MACHINE SCREWS FOR CLEANOUT COVERS
13) GAS SLEEVE VENT TO BE PER PLAN
03/03/2011 PLUMBING - FINAL Prior to Final Inspectn