Permit: T10CM01801

Parcel: 11901076A


Addresses:

3346 S 6TH AV #100


Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T10CM01801

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
10/08/2011 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
10/06/2011 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
PROVIDE TEST ON PIPELINE,
RPB REQUIRES 12" MINIMUM FROM FINISH GRADING TO DRAIN OPENING, AND RISERS REQUIRE PROTECTION FROM CONCRETE (CANNOT BE DIRECTLY EMBEDDED IN CONCRETE.
09/30/2011 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) FROM METER THRU RPB TO 5' FROM BLDG WATER TEST OK
09/29/2011 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) 3" COPPER SERVICE STUB OUT 5' OK