Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM01801
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2011 | ELECTRIC - INTERMEDIATE | Approved | ||
10/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RECEIVED LETTER OF TORQUE 2) USE CORRECT WATER/GAS BOND CLAMP 3) STILL NEED COMPLIANCE WITH NOTES: #3 AND 10 4) ALSO CAN USE FORMULA 310.15 6 C NEC. |
|
10/26/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSPECTION FOR SES EQUIPMENT 2) REATTACH GROUND ELECTRODE CONDUCTOR TO 2ND GROUND ROD OR INSTALL NEW 2) NEED LETTER OF TORQUE 3) COMPLETE LOAD TERMINATIONS 4) BOND BLDG STEEL, WATER AND GAS PER 250.104 NEC |
|
10/21/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FILL UNUSED OPENINGS IN BOXES 2) TIGHTEN LOOSE FITTINGS CONDUIT AND M/C 3) DERATE CONDUCTORS FOR GUTTER 366 4) CONDUCTOR DERATING IN RACEWAY 310.15 5) PROTECT CONDUCTORS 300.4 6) CLEAN SURFACE UNDER GROUND BAR 250.12 7) TIGHTEN GROUND TERMINALS LIGHT FIXTURES 8) PANEL DIRECTORIES TO BE PER 408.4 9) BOXES 314.20 & 21 10) VERIFY LISTING FOR MONEY CAHNGERS AND SOAP DISPENSORS 11) PULL BOX TO BE PER 314.28 12) PROVIDE LETTER OF TORQUE FOR NEW SWTCH GEAR 13) FUSES NOT PER PLANS 14) TIGHTEN GROUNDED CONDUCTORS SWITCHBOARD |
|
05/17/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK RESTROOM WALLS/HARD LIDS |
|
02/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK HARD LID MAIN FLOOR/LAUNDRY AREA 2) OK WALLS SECURE ROOM |
|
02/03/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |