Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T10CM01795
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2011 | MECHANICAL - INTERMEDIATE | Approved | ||
10/25/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | ||
10/24/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | ||
10/06/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE STIFFENERS IN DUCT (BASEMNET, PARKING AREA) PER SMACNA STANDARDS OR AS NEEDED |
|
10/03/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | ||
08/26/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | ||
08/17/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | ||
08/10/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | AH2.2 & AH3.2 CONNECTION TO CHILLED WATER (110 PSI TEST) OK HYDRONIC PIPING IN MECH 3 OK (110psi TEST) |
|
08/04/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | ||
07/29/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) HYDRO TEST AT 2ND FLOOR F.C.-2.5 3RD FLOOR F.C.-3.3, F.C.-3.5 100 PSI OK 2) SUPPLY AIR DUCT IN WEST STAIRWELL FROM 9TH FLOOR TO 1ST FLOOR OK |
|
07/13/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | ELEVATOR PRESSURIZATION FANS & DUCT OK | |
06/24/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | ||
06/15/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | ||
05/13/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | ||
05/11/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/10/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | ||
05/04/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | LEVEL 6 BOOSTER FANS UNDER FLOOR OK EAST OF LINE D | |
04/29/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | ||
04/28/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | BOOSTER UNITS LEVEL 5 WEST OF LINE D INSTALLED OK UNDER FLOOR | |
04/07/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/25/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | FIRE DAMPERS FROM SHAFTS ON 5TH FLOOR OK. STILL NEED TO SEE FLANGE PROPERLY ATTACHED WHEN OUTER LAYER OF SHEET ROCK APPLIED. | |
03/23/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL- FOR ROUND FIRE DAMPERS FRAME AND SQUARE OPENING AND FINISH WITH THE SUPPLIED FLAT PLATE ON THE OUTSIDE OF WALL AND SCREW TO FRAMING. |
|
03/15/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | DUCTS INSTALLED FROM SHAFT AT ELEVATOR WITHOUT REQUIRED FIRE DAMPERS. SPOKE TO GARRETT OF RYAN CORP ABOUT THIS ISSUE. | |
03/15/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WALKED JOB WITH J. MILITELLO TO FAMILIARIZE HIM WITH THE PROJECT 2) ADDRESSED GREASE DUCT CLEANOUTS AND MAKE UP AIR |
|
03/10/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ON SITE MEETING WITH G.C. AND MECHANICAL CONTRACTORS |
|
03/04/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | 2 LAYERS FIRE WRAP ON 4 FABRICATED SECTIONS OF DUCT OK | |
03/03/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | SUN MECHANINCAL NOT READY TO PROVIDE PRETEST ON GREASE DUCT. SECTIONS OF DUCT DELIVERED TO SITE OK AND PERMISSION GIVEN TO SUN TO WRAP AND INSTALL ENTIRE LENGTH IF THEY PROVIDE MANOMETER TEST RATHER THAN SMOKE TEST ON COMPLETED INSTALLATION. | |
02/28/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |