Permit: T10CM01795

Parcel: 11717023D


Addresses:

88 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM01795

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/01/2011 ELECTRIC - INTERMEDIATE Approved SEE BUILD-OUT ACTIVITY T10CM03478 FOR FINAL INSPECTION INFORMATION
10/12/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/07/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) TIGHTEN LOOSE FITTINGS AT TIBER FLOW UFD'S
2) WHERE IS MASTER GFCI FOR BATHROOMS
10/06/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO RFD CONTROLS LINE SIDE B1, B2, B3
09/30/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DISCONNECTING MEANS NEEDED FOR ROLL UP DOOR MOTORS
09/29/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK PANELS PSBMPOP, HMPOP, PMPOP, H4W, H4E, S5E, H5W,H6E, H6W, P3WA, P3WB, T3W, P3EA AND P3EB
2) ADDRESS LABELING ISSUES WITH ONE LINE AND EAST ELECTRIC PANEL A & B'S
09/23/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROTECT CONDUCTERS AT BOXES FROM SHARP METAL EDGES
2) WILL NEED ARC SHEILDS 314.2
3) NEED JUNCTION BOX ACCESS LEVELS B1,B2, B3 ELEVATOR LOBBIES
4) FILL UNUSED BOX OPENINGS
5) VERIFY CONDUCTER DEPATING 310.15
6) BOXES CUT ON ROUNDS 314.2
7) LABEL CONDENSING UNIT DISCONNECTS
8) IDENTIFY FIRE ALARM BOXES 760.10
09/22/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SEAL TOP OF FIRE PUMP CONTROLLER AND JOCKEY PUM CONTROLLER FOR WET LOCATION
09/20/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/19/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/16/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 8-1 1/4" PVC OUT 30' FOR EV CHARGERS
2) OK 2-2" PVC OUT 40' FOR RAIN PUMP SYSTEM
3) OK 1-1" PVC OUT 40' FOR BOLLARDS
4) OK WALL LIGHTS STAIRWELL #2 B3 THRU 9 FLOORS
5) VERIFY LISTING FOR SUMP PUMPS
09/15/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
STAIRWELL #2:
1) PROTECT CONDUCTORS FROM SHARP METAL EDGES
2) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20
09/12/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CONDUITS STAIRWELL #2 FOR "AREA OF NOTIFICATION"
09/09/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/08/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NOTE: GENERATOR IS LABELED AND LISTED
09/06/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) MAINTAIN DEDICATED SPACE ABOVE H1W
08/25/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/24/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/23/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/22/2011 ELECTRIC - INTERMEDIATE Partial Approval LIGHTS IN CHILLER ROOM- NO SHEET METAL THREAD SCREWS 250.8
08/19/2011 ELECTRIC - INTERMEDIATE Partial Approval DID GENERAL WALK THRU FOR COMM. & MECHANICAL ROOMS
OK ACC'S WORK FLOORS 5-9

1. HAVE BUILDING INSPECTOR VERIFY CABLE IN FLOOR/CEILING PASS THRU'S
08/18/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 3/4" PVC CONDUIT COLUMN TO COLUMN NORTH SIDE
08/17/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS COMM ROOM #2 1ST FLOOR
08/16/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CPA AND THCP
2) SWITCHBOARD DSCPA 408.3
08/15/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WEST SIDE ELECTRICAL LOBBY HALL
08/11/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ATRIUM LOBBY CEILING, ELEVATOR LOBBY ON 1ST FLOOR AND HALL EAST SIDE
08/10/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CONDUCTOR SUPPORT ON VERTICAL RISE PER 300.19
2) OK HS?CP, TSBC
3) OK WALLS 310, 410, 510,610,710,810,910 STAIRWELL #2
08/09/2011 ELECTRIC - INTERMEDIATE Partial Approval
08/08/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS ELEVATOR LOBBY AND STORAGE B-1 & B-3
2) OK WALLS ELEVTOR LOBBY B-1
3) PROTECT FLEX CONDUITS IN SHALLOW WALLS B-1,B-2 & B-3
4) USE APPROVED STRAPPING METHODS FOR SECURING FLEX CONDUIT
08/05/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK VFD'S CPA1 & 2, ? 3.1 LIEBERT
08/04/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/04/2011 ELECTRIC - INTERMEDIATE Partial Approval
08/02/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CHILLER #2 ON ROOF AND #1 AT UPS PANEL
2) FINISH LOOSE FITTINGS AND SUPPORTS ON ROOF
3) TALKED WITH RICK B. (RYAN) ROOF PROGRESS
08/01/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BOND JUNCTION BOX
2) LOOSE FITTINGS AND STRAPS
3) STILL WORKING CLEARANCES
07/27/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/26/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUPPORT AT CODE INTERVALS ON 2ND FLOOR BEHIND DOOR WALL
2) FINISH SECURING BUSS DUCT TO SUPPORTS
3) SECURE EQUIPMENT-SWITCH BOARDS, ATS, UPS TO FLOOR
4) TIGHTEN LOOSE CONDUCTOR TERMINATIONS TRANSFORMER HCP
07/25/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) GENERAL WALK THRU-BUSS DUCTS WILL BE READY TOMORROW AND UPS SWITCH BOARDS
07/22/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) GENERAL WALK THRU
07/21/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CANS WEST SIDE NORTHWEST CORNER
2) OK HL1W,T1W,P1WA,UPS1W,SP1W,BUSS PLUG HL1W,BUSS PLUG HSBG,HSBG AND PG
3) FINISH LABELING BUSS PLUGS
07/20/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CAN NORTH END WEST SIDE
2) ADDITIONAL SUPPORTS NEEDED FOR MORE THAN ONE EXTENTION BOX/RING
07/19/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CORRECTIONS STAIRWELL #2 3RD FLOOR AND DOWN
2) OK ENTRY DOOR WALL EXIT PASSAGE 1ST FLOOR #136
07/18/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :* GENERAL WALK THROUGH
07/14/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PANEL PR & XFMR TPR
07/13/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DISCUSSED SCHEDULING AND PROGRESS
07/12/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK PSBR (ALL) AND TSBR
2) OK TO USE FLEX CONDUIT TO TRANSITION DUE TO SPACE
07/11/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO MAINS HL9W, HL8E,P8EA,HL8W,P8UA,HL7E,P7EA,H67W,P7WA,HL6E,P6EA,HL6W,HL5E,P5EA,HL5W,P5WA
2) OK TRANSFORMER T8E,T8W,T7E,T7W,T6E,T6W,T5E,T5W
3) OK REPAIRS BUSS DUCTS 1,2,6 & 7
4) PANEL P8WA MISSING PARTS
5) ADD ADDITIONAL BUSS DUCT SUPPPORTS AT COUPLINGS AS DISCUSSED
6) MAINTAIN ILLUMINATION AT EQUIPMENT
07/08/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK "HSBR" PANEL
2) OK STAIRWELL 210,110,B1,B2 & B3
07/07/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CANS HALL CEILING ON 4TH FLOOR WEST
07/06/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DISCUSSED WORKING SPACE PERM 110.26 AT COOLING TOWERS WITH TODD OF ROSENIDIN AND RICK BENJAMIN OF RYAN, RICK WAS GOINTG TO ADD A PLATFORM AT CT2 AND MOVE COPPER PIPES AT OT1 & 3
07/01/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK BUSS DUCT 3 TO ENERGIZE AFTER CORRECTIONS
2) OK PANEL ELEV AND XFMR ELEV
3) SUPPORT BUSS DUCTS AT "ATF'S" AS DISCUSSED
4) DO NOT FOLD CONDUCTOR AT XFMR LUGS
06/30/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CONNECTIONS FOR AND AT "DPELEV"
2) OK BONDING AT ATF
06/29/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FINISH STRAPPING AND SUPPORT BUSS DUCT AT 1 WEST
2) MEET WITH ELEVATOR INSPECTOR TO DETERMINE JURISDICATION OF ROOM
06/28/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK HARD LIDS 107,108 & 115
06/27/2011 ELECTRIC - INTERMEDIATE Partial Approval
06/27/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK STAIRWELL (1) 108-908
2) OK STAIRWELL (3) 120-220
3) OK HARD LIDS 501,601,701 AND 801 EXCEPT AS NOTED
4) MISSING EM LIGHTS 501
06/24/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/24/2011 ELECTRIC - INTERMEDIATE Partial Approval LEVEL 4 PARAPET CHANGES OK
06/23/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* 1) MAINTAIN WORKING CLEARENCE AT COOLING TOWERS 1,2,3
2) NOTE: ELEVATORS FOR INTERIOR ARE ON TEMP POWER
06/22/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :
1) GENERAL WALK THRU AND ANSWER QUESTIONS
06/21/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 2 CORE REDO AFTER CORRECTIONS
2) NEED BANG PLATE PROTECTION FOR FLEX AND M/C CABLE
06/16/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) STAIR WELL #1 LOOSE FITTINGS
2) SUPPORT CONDUIT ON HORIZONTALS
06/15/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NOTE: AT MULTI POLE DUCT TRANSITIONS MAY NEED ADDITIONAL TOP SUPPORTS
06/14/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) NOTE: BUSS DUCTS HAVE BEEN WATER DAMAGED-BEING REMOVED AND SENT BACK TO FACTORY FOR EVALUATION AND REPAIR
06/13/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK HL4E, H4E, HL5E, HL6E, HL7E, H7E, HL8E, H8E, HL9E AND H9E
2) AIR HANDLERS: TIGHTEN LOOSE FITTINGS, PROPERLY STRAP CONDUIT TO FLOOR AND WALLS, REDUCING WASHERS NOT INSTALLED CORRECTLY, UNDERSIZED WIRE NUTS AND SEAL TIGHT NOT FULLY INSTALLED INTO FITTING
2) DO NOT STACK LUGS IN TRANSFORMER
06/08/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK BUSS SUPPORTS ON FLOOR 9 EAST AND WEST ELECT ROOMS
2) OK CHILLER AND CEILING TOWER #1
3) TIGHTEN AND SECURE 4" TO CHILLER
4) NEED ACCESS TO BUSS DUCTS 5 & 9 ON FLOOR 2
06/07/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) TIGHTEN LOOSE FITTINGS 209 SOUTH AND TIGHTEN CARD READER BOX
2)_ CLIMATIC FOR SUN MECH: TIGHTEN ALL LOOSE FITTINGS AND STRAP RACEWAYS TO FLOOR-ALL LEVELS
06/06/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS 102,103,104,105,106,107, 202, 302, 402, ATRIUM WALL AT 2ND FLOOR FOR LIGHTS
1. MECHANICAL ROOM 108 COVERED WITHOUT INSPECTION
2. STRAP CONDUITS DOWN FROM CEILING AT VESTABULE FOR ELEVATORS FLOOR 1-9
06/04/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FILL UNUSED OPEININGS IN TOP OF SES
2) SUPPORT BD #1 ABOVE SES
3) FINISH SUPPORTS ON HORIZONTALS BBD 1,2,3,6,7 & 5
4) NEED VERTICAL SUPPORTS ELECTRIC ROOM 1E, 1W, 3E AND 9W
5) SUPPORT COUPLINGS AT WALL DOWN TO ELECTRIC ROOM 1W
6) SUPPORT DUCT UNDER DPR
7) NEED PLUG CAP ON HORIZONTAL RUN 1ST FLOOR
8) ADD STABILIZATION WASHERS UNDER FLOOR 9E
9) NEED CENTER SUPPORT VERTICAL 2W
10) MAINTAIN DEDICATED SPACE BELOW SB1E AND UPS1E
11) OK BUSS TO PANEL TAPS DPR, DSCPB, HSB1W
12) OK BUSS DUCTS 4 & 8 FROM SES TO CENTRAL PLANT
13) OK 1, 2, 6 & 7 HORIZONTAL ON 1ST FLOOR BUSS DUCTS
14) OK 1, 2, 6 & 7 VERTICAL FLOORS 1 TO 9 BUSS DUCTS
15) OK BUSS PLUGS #4E, HL4E, H4W, HL4W, H5E, HL5E, HL5W, H5W, H6E, HL6E, H6W, HL6W, H7E, HL7E, H7W, HL7W, H8E, HL8E, H8W, HL8W, HL9E, HL9W AND H9W
06/03/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) VERIFY WITH ENGINEER FOR METHOD OF GROUNDING ELECTRODE TAPS 250.30 (A)
06/02/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DISCUSSED GROUNDING SITUATIONS-GROUNDING ELECTRODE CONDUCTOR AND GROUND BARS
2) NEED ACCESS TO JUNCTION BOXES ABOVE HARD LIDS
06/01/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RECEIVED BREAKER TEST REPORTS-NOT ALL HAVE GFI TEST REPORTS
05/31/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* OK 502, 602, 702, 802, 902
05/27/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 3 CANS OUTSIDE 114
2) SUPPORT 2 1/2" EMT WITHIN 3' OF SES
05/25/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 3 CANS OUTSIDE 114
2) SUPPORT 2 1/2" EMT WITHIN 3' OF SES
05/23/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 4" EMT COMM1 (103) TO COMM2 (112)
2) ANSWER QUESTIONS FOR ROOF
05/20/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CRANE HOLD GROUND LEVEL EMT, BOX AND SLEEVES
2) OK FEEDER CONDUITS "PG", "HGB", "HMPOP" AND "PMPOP"
3) OK 8-4" EMT "MPOP" TO COMM 1 (103)
4) TIGHTEN LOOSE FITTINGS 4" EMT COMM1 (103) TO COMM2 (112)
5) TIGHTEN STRUT RAIL SUPPORTS
05/19/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/18/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ANY AND ALL MODIFICATION TO SWITCH GEAR NEED NTRL EVALULATION
05/17/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE CONDUCTORS TO BE PER 230.7, 408.3 AND 352.46
05/16/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK UNDER FLOOR 612
2) OK 4 BOXES AND STUBS SOUTHSIDE OF GARAGE LIGHTS
3) ANSWERED QUESTIONS REGARDING FIRE PUMP
05/13/2011 ELECTRIC - INTERMEDIATE Partial Approval
05/11/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS R02 & R03
2) PROTECT CONDUCTORS AT RACEWAYS 300.4 & 408.3
3) PROTECT TENT AT TRANSITION BLOCK TO CONDUITS LEVEL 1 & 2 MAINTENANCE ROOM
05/10/2011 ELECTRIC - INTERMEDIATE Partial Approval
05/09/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ROOF:
1) PROTECT SEAL TITE FROM SHARP METAL EDGE AH-10.1, 10.2 AND 10.3
2) TIGHTEN LOOSE FITTINGS AH-10.3
3) NO MORE THAN 360 DEGREE IN CONDUIT RUNS
9TH FLOOR:
1) OK RECESSED CANS EAST TERRANCE
05/06/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/05/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK HARD LIDS 906, 907, 917 & 918
05/04/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/03/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ON CORE 203-205, 208, 211-213
OK LIDS 206, 207
OK SOFFIT IN RM 340
OK WALLS 311
2ND FLOOR
1) PROTECT M/C INSIDE OF CHANNEL STUDS
2) SECURE CONDUIT BETWEEN BATHROOMS
05/02/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* OK TO CLEAR TO MAIN BREAKERS
ONLY A & B
OK HAND LIDS 807, 806
1)DONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT
2) DO NOT ENERGIZE FIRE PUMP CONTROLER OR SES "MSE"
3)PROVIDE PROTECTION FOR CONDUITS AT SES "A"
4) NEED GFI TEST
RECIEVED MEGER TEST SHEETS & TORQUE SHEETS
04/29/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/28/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/27/2011 ELECTRIC - INTERMEDIATE Partial Approval 3RD FLOOR ABOVE CIEL DONE LAST WEEK
04/27/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* FOR SWITCH GEAR: WILL NEED LETTER VERIFYING TORQE OF EQUIPMENT, ILLUMIMATION, LOCK OUT/TAG OUT PROCEDURES, SECURED IN PLACE
* PLEASE VERIFY FAULT CRRENT AT 4000A MAINS A & B
04/26/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/25/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/21/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 2ND FLOOR BATHROOMS COVERED WITHOUT INSPECTION
2) 3RD FLOOR BATHROOMS NOT FINISHED
3) OK 1ST FLOOR CANNS LOBBY ENTRANCE
4) OK 1ST & 4TH FLOOR BOXES, FLEX CONDUIT AND EMT FOR CATHEDRAL LIGHTING
5) 300.3 (C) (2) (A) & (B)
6) CONDUITS IN SHAFTS FOR FIRE ALARM CONTROL WIRING IS INSTALLED ONLY TO MINIMUM CODE ADDITONAL SUPPORTS MAYBE NECESSARY
04/20/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CIELINGS IN FLOOR 2 + 3 BATH ROOMS NOT READY
2. VERIFING SUPPORT OF RACEWAYS W SHAFTS FOR FIRE CONTROL CABLES
04/19/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/19/2011 ELECTRIC - INTERMEDIATE Partial Approval
04/18/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/14/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/12/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/11/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/08/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/07/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS R04 AND CORE EXTERIOR WALLS
2) OK EAST WALL ROOF FOR WALL LIGHTS
04/05/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/04/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/01/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 610, 611, 613, 608, EAST AND WEST SHAFT 6TH
2) FINISH 602
03/31/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO WORK PROGRESS
03/30/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 513 WALLS
03/29/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ROOMS 511 AND STAIRWELL
2) OK RUNS FOR TI ON BATHROOM WALL-CONDUIT UP WALL
3) OK INSIDE BOTH SHAFTS ON #5
4) FINISH 502 & 513
5) FINISH 602, 611, 613, STAIRWELL AND TI STUBS
03/28/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/25/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/24/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/23/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
LEVEL B-2
FILL UNUSED OPENINGS IN FIXTURES 110.12
03/22/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PULL BOXES TO BE PER 314.28 LOWER LEVELS
2) VERIFY 360 DEGREE OF RUN THRU CEMENT AND CONDUITS
03/21/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS ROOMS #403, 405, 503, 505, 603, 605, 703, 705, 803, 805 AND 905
03/17/2011 ELECTRIC - INTERMEDIATE Partial Approval FLOORS 4 THROUGH 9 OK TO COVER ELECTRICAL ROOM WALLS BY ELEVATOR.
03/17/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS ROOMS 202-205, 302-305
2) OK AS MARKED WALLS 208,211,308 & 311
03/15/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/14/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS 912 & 812
03/11/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/10/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) TIGHTEN LOOSE FITTINGS (812)
03/09/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 6,7,8 & 9 FLOORS TO POUR STUBS
2) OK WALLS 512,612,712 & 812
03/08/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SEPERATE EM CIRCUIT AND REGULAR CIRCUIT FOR LIGHTING IN BOXES, ALSO NOTE IF MORE THAN 300V BETWEEN DEVICES
2) DO NOT POUR EMT ENCASEMENTS UNTIL INSPECTED
3) OK WALLS #202,203,204,212,304,312,404,412,606,607,706 AND 707
4) OK FLOOR STUBS: FLOORS 2-7
03/04/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SECURE CONDUIT IN WALLS
2) PROTECT FLEX IN STUD CHANNELS
03/03/2011 ELECTRIC - INTERMEDIATE Partial Approval
03/02/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALL 406, 407, 506 AND 507
03/01/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) JUNCTION BOX TO BE ACCESSIBLE 314.20 WILL APPLY
2) OK WALLS 106, 107, 206, 207, 306 AND 307
02/28/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/25/2011 ELECTRIC - INTERMEDIATE Partial Approval LEVEL 4 EAST UNDER CONST.
02/21/2011 ELECTRIC - INTERMEDIATE Partial Approval LEVEL 4 SW CONDUIT AND OUTLETS OK
02/08/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/08/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OK DECK 3 SOUTH + EAST
OK FIRE, COMM + CAMERA
FINISH POWER + LIGHTING ROOF WEST
02/07/2011 ELECTRIC - INTERMEDIATE Partial Approval ELECTRICAL INSIDE COLUMNS AND SHEARWALLS OK TO LEVEL 4 S AND SW SECTIONS.
02/04/2011 ELECTRIC - INTERMEDIATE Partial Approval
02/02/2011 ELECTRIC - INTERMEDIATE Partial Approval ROOF EAST SIDE OK TO COVER CONDUITS AND OUTLETS
02/01/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROOF DECK NORTH EAST
ENT, BOXES & GROUNDS
01/31/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/25/2011 ELECTRIC - INTERMEDIATE Partial Approval LEVEL 9 WEST AND RAMP 2-3 OK TO COVER CONDUITS AND OUTLETS
01/24/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/20/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FIRE ALARM, SECURITY + CAMERA BOXES + ENT
1. FINISH LIGHTING POWER + EMERGENCY
01/18/2011 ELECTRIC - INTERMEDIATE Partial Approval LEVEL 9 NE OK TO COVER. LEVEL 2 SW OK TO COVER. COLS & SHEARWALLS LEVEL 8 AND RAMP 1-2 OK TO COVER.
01/13/2011 ELECTRIC - INTERMEDIATE Partial Approval LEVEL 8 WEST SIDE IN-SLAB CONDUITS AND OUTLETS OK TO COVER
01/13/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 8TH DECK NORTHWEST BOXES, EMT, BUSS DUCT SLEEVES AND PASS THRU SLEEVES
01/12/2011 ELECTRIC - INTERMEDIATE Partial Approval
01/07/2011 ELECTRIC - INTERMEDIATE Partial Approval ELECTRICAL OUTLETS AND CONDUITS IN RAMP FROM LEVEL 1 - 2 OK.
01/06/2011 ELECTRIC - INTERMEDIATE Partial Approval CONDUITS AND OUTLETS IN SLAB LEVEL 8 EAST OK.

ONGOING PLACEMENT OF OUTLETS AND CONDUITS IN MASONRY AT PLAZA LEVEL ARE OK
01/04/2011 ELECTRIC - INTERMEDIATE Partial Approval LEVEL 7 WEST IN SLAB ELECTRICAL OUTLETS AND CONDUIT OK
12/30/2010 ELECTRIC - INTERMEDIATE Partial Approval NEED TO RELOCATE OUTLETS AND CONDUITS IN BEAM LINE 15 FROM A-C. CANNOT HAVE PLASTIC IN CRUSH ZONES OF TENDONS. CONDUIT BURNING DECK AT J14 AND TOO CLOSE TO TOP OF SLAB AT I13.
12/27/2010 ELECTRIC - INTERMEDIATE Partial Approval LEVEL 7 NE OK TO COVER CABLES, CONDUITS AND OUTLETS IN SLAB
12/23/2010 ELECTRIC - INTERMEDIATE Partial Approval LEVEL 6 NW OK TO COVER CABLES AN CONDUITS IN FLOOR SLAB.
12/20/2010 ELECTRIC - INTERMEDIATE Partial Approval CENTRAL AREA OF SOUTH PLAZA LEVEL CONDUITS AND CABLES OK
12/17/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/16/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK EMT AND BOXES 6 DECK NORTHEAST
12/07/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK BOXES AND EMT
2) DECK 5 NORTHEAST
12/01/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/30/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FINISH RACKS AND TIES TO SES "B"
2) SES "B" PULL BOX IS 48" WIDE-314.28 (A) (2) DUE TO DESIGN THIS WILL BE ALLOWED
11/29/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) LOOKED AT PULL SECTIONS (?)
11/23/2010 ELECTRIC - INTERMEDIATE Partial Approval NE LEVEL 4 OK FOR ELECTRICAL IN SLAB
11/23/2010 ELECTRIC - INTERMEDIATE Partial Approval CABLES AND CONDUITS IN COLS LEVEL 4 NE OK
11/23/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 4 DECK NORTHEAST EXCEPT EDGES
11/19/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/17/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/17/2010 ELECTRIC - INTERMEDIATE Partial Approval CONDUITS AND OUTLETS INSIDE FLOOR OK TO COVER LEVEL 3 NW
11/12/2010 ELECTRIC - INTERMEDIATE Partial Approval CABLES AND CONDUITS IN COLS AT NE LEVEL 3 OK
11/11/2010 ELECTRIC - INTERMEDIATE Partial Approval NE LEVEL 3 CONDUITS AND OUTLETS IN SLAB OK. OUTLETS ADDED FOR LIGHTING THAT ARE NOT YET ON APPROVED PLAN BUT WILL BE ON TI PLAN IN AREA 1-4/H-J
11/10/2010 ELECTRIC - INTERMEDIATE Partial Approval CONDUITS AND OUTLETS IN CONCRETE RAMP FROM B1 TO PLAZA LEVEL OK
11/08/2010 ELECTRIC - INTERMEDIATE Partial Approval CONDUITS AND CABLES INSIDE COLS AND SHEARWALLS SE LEVEL B1 OK

CONDUITS AND CABLES INSIDE COLUMNS NW LEVEL 2 OK
11/05/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/04/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/04/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) MET WITH CONTRACTOR, ELECTRICIAN AND GARRETT, TO DISCUSS COMM ROOM RACEWAYS-EMT WILL BE STUBBED UP AND WE WILL WAIT ON ENGINEER
11/03/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/02/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/02/2010 ELECTRIC - INTERMEDIATE Partial Approval CABLES OK IN SHEARWALLS NE LEVEL 2 OK
11/01/2010 ELECTRIC - INTERMEDIATE Partial Approval CABLES AND CONDUITS INSIDE COLUMNS AND SHEAR WALLS NW LEVEL B1 OK

CABLES AND CONDUITS INSIDE COLUMNS NE LEVEL 2 OK
10/30/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/29/2010 ELECTRIC - INTERMEDIATE Partial Approval NE LEVEL 2 OK TO PLACE FLOOR SLAB. CONDUITS AND OUTLETS OK.
10/29/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) SECURE AND STRAP FOR SNORKEL 90 DEGREE AND BLOCKOUTS LEVEL 2 ? NORTH EAST
10/28/2010 ELECTRIC - INTERMEDIATE Partial Approval OK LEVEL B1 SOUTH A-E
10/26/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK B-1 TO B-2 RAMP SOUTHEAST
2) BOXES WITH WRONG KO PUNCHED OUT TO BE REPLACED- DUCT TAPE NOT AN APPROVED METHOD
10/26/2010 ELECTRIC - INTERMEDIATE Partial Approval COLUMN AND SHEARWALL RUNS NORTH SIDE LEVEL 1 APPROVED.
10/19/2010 ELECTRIC - INTERMEDIATE Partial Approval SOUTH EAST AREA OF LEVEL B2 OK FOR IN SLAB
10/19/2010 ELECTRIC - INTERMEDIATE Partial Approval 1) PLAZA LEVEL NW- OK TO COVER ELEC IN SLAB
2) COLS AND SHEAR WALLS PLAZA LEVEL NE CONDUITS AND BARE CONDUCTORS OK. OK TO COVER
3) CONDUCTORS OK IN LEVEL B2 SW COLUMNS
10/15/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK NORTHEAST DECK B1-B2 ENT, BOXES, PVC FOR POWER, SECURITY, CO-2, + DATA
10/13/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK GENERATOR AREA PLAZA
2) SUPPORT EMT PER CODE
3) FINISH RUNS
10/12/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK SOUTH WST EMT, BOXES, SECURITY,POWER AND DATA-DECK B-3/B-2
10/05/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK COLUMNS AND SHEARWALL BOXES & PVC B-1 NORTH WEST
10/04/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/02/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/01/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/30/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK RECEPTS AND LIGHTS IN COLUMN WALLS STAIR #2 ON B-1
09/29/2010 ELECTRIC - INTERMEDIATE Partial Approval OK TO CLOSE AND PLACE COLUMNS AND SHEAR WALLS LEVEL B1 @ E-J/3-11
09/27/2010 ELECTRIC - INTERMEDIATE Partial Approval IN SLAB CONDUITS LEVEL B1 AREA 3-11/E-J OK
09/27/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) OK B-1 DECK, CONDUITS, BOXES, SECURITY AND FIRE ALARM NORTH EAST CORNER
09/27/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 2 LIEBERT UNITS IN UPS ROOM
2) OK CONDUIT AND BOXES FLOOR 2ND, EAST OF 'D' SOUTH OF CORE AND ROOMS 254 AND 255
3) FILL UNUSED OPENING FA BOX 6TH FLOOR
4) STRAP FIRE CONDUITS CORRECTLY 4TH AND 5TH FLOOR
5) JUNCTION BOXES TO BE ACCESSIBLE 5TH FLOOR
6) SEPERATED FLEX CONNECTOR 5TH FLOOR
7) SUPPORT FA BOXES OVER ONE EXTENTION ALL FLOORS
09/23/2010 ELECTRIC - INTERMEDIATE Partial Approval OK LEVEL B2 AREA A-E/3-11 FOR IN SLAB ELECTRICAL
09/22/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK POWER RUNS B2 NEW DECK
09/21/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) MAINTAIN CLEARANCES WITH POST TENSION CABLES
09/17/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK NORTH EAST IN B-2 DECK
2) PVC CONDUITS, BOX FOR LIGHTS, FIRE ALARM AND SECURITY