Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM01795
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2011 | ELECTRIC - INTERMEDIATE | Approved | SEE BUILD-OUT ACTIVITY T10CM03478 FOR FINAL INSPECTION INFORMATION | |
10/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) TIGHTEN LOOSE FITTINGS AT TIBER FLOW UFD'S 2) WHERE IS MASTER GFCI FOR BATHROOMS |
|
10/06/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO RFD CONTROLS LINE SIDE B1, B2, B3 |
|
09/30/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DISCONNECTING MEANS NEEDED FOR ROLL UP DOOR MOTORS |
|
09/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PANELS PSBMPOP, HMPOP, PMPOP, H4W, H4E, S5E, H5W,H6E, H6W, P3WA, P3WB, T3W, P3EA AND P3EB 2) ADDRESS LABELING ISSUES WITH ONE LINE AND EAST ELECTRIC PANEL A & B'S |
|
09/23/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROTECT CONDUCTERS AT BOXES FROM SHARP METAL EDGES 2) WILL NEED ARC SHEILDS 314.2 3) NEED JUNCTION BOX ACCESS LEVELS B1,B2, B3 ELEVATOR LOBBIES 4) FILL UNUSED BOX OPENINGS 5) VERIFY CONDUCTER DEPATING 310.15 6) BOXES CUT ON ROUNDS 314.2 7) LABEL CONDENSING UNIT DISCONNECTS 8) IDENTIFY FIRE ALARM BOXES 760.10 |
|
09/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SEAL TOP OF FIRE PUMP CONTROLLER AND JOCKEY PUM CONTROLLER FOR WET LOCATION |
|
09/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
09/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
09/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 8-1 1/4" PVC OUT 30' FOR EV CHARGERS 2) OK 2-2" PVC OUT 40' FOR RAIN PUMP SYSTEM 3) OK 1-1" PVC OUT 40' FOR BOLLARDS 4) OK WALL LIGHTS STAIRWELL #2 B3 THRU 9 FLOORS 5) VERIFY LISTING FOR SUMP PUMPS |
|
09/15/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* STAIRWELL #2: 1) PROTECT CONDUCTORS FROM SHARP METAL EDGES 2) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 |
|
09/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CONDUITS STAIRWELL #2 FOR "AREA OF NOTIFICATION" |
|
09/09/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NOTE: GENERATOR IS LABELED AND LISTED |
|
09/06/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) MAINTAIN DEDICATED SPACE ABOVE H1W |
|
08/25/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
08/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
08/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
08/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | LIGHTS IN CHILLER ROOM- NO SHEET METAL THREAD SCREWS 250.8 | |
08/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | DID GENERAL WALK THRU FOR COMM. & MECHANICAL ROOMS OK ACC'S WORK FLOORS 5-9 1. HAVE BUILDING INSPECTOR VERIFY CABLE IN FLOOR/CEILING PASS THRU'S |
|
08/18/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 3/4" PVC CONDUIT COLUMN TO COLUMN NORTH SIDE |
|
08/17/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS COMM ROOM #2 1ST FLOOR |
|
08/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CPA AND THCP 2) SWITCHBOARD DSCPA 408.3 |
|
08/15/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WEST SIDE ELECTRICAL LOBBY HALL |
|
08/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ATRIUM LOBBY CEILING, ELEVATOR LOBBY ON 1ST FLOOR AND HALL EAST SIDE |
|
08/10/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CONDUCTOR SUPPORT ON VERTICAL RISE PER 300.19 2) OK HS?CP, TSBC 3) OK WALLS 310, 410, 510,610,710,810,910 STAIRWELL #2 |
|
08/09/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
08/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS ELEVATOR LOBBY AND STORAGE B-1 & B-3 2) OK WALLS ELEVTOR LOBBY B-1 3) PROTECT FLEX CONDUITS IN SHALLOW WALLS B-1,B-2 & B-3 4) USE APPROVED STRAPPING METHODS FOR SECURING FLEX CONDUIT |
|
08/05/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK VFD'S CPA1 & 2, ? 3.1 LIEBERT |
|
08/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
08/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
08/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CHILLER #2 ON ROOF AND #1 AT UPS PANEL 2) FINISH LOOSE FITTINGS AND SUPPORTS ON ROOF 3) TALKED WITH RICK B. (RYAN) ROOF PROGRESS |
|
08/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BOND JUNCTION BOX 2) LOOSE FITTINGS AND STRAPS 3) STILL WORKING CLEARANCES |
|
07/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/26/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPPORT AT CODE INTERVALS ON 2ND FLOOR BEHIND DOOR WALL 2) FINISH SECURING BUSS DUCT TO SUPPORTS 3) SECURE EQUIPMENT-SWITCH BOARDS, ATS, UPS TO FLOOR 4) TIGHTEN LOOSE CONDUCTOR TERMINATIONS TRANSFORMER HCP |
|
07/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GENERAL WALK THRU-BUSS DUCTS WILL BE READY TOMORROW AND UPS SWITCH BOARDS |
|
07/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GENERAL WALK THRU |
|
07/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CANS WEST SIDE NORTHWEST CORNER 2) OK HL1W,T1W,P1WA,UPS1W,SP1W,BUSS PLUG HL1W,BUSS PLUG HSBG,HSBG AND PG 3) FINISH LABELING BUSS PLUGS |
|
07/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CAN NORTH END WEST SIDE 2) ADDITIONAL SUPPORTS NEEDED FOR MORE THAN ONE EXTENTION BOX/RING |
|
07/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CORRECTIONS STAIRWELL #2 3RD FLOOR AND DOWN 2) OK ENTRY DOOR WALL EXIT PASSAGE 1ST FLOOR #136 |
|
07/18/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* GENERAL WALK THROUGH | |
07/14/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PANEL PR & XFMR TPR |
|
07/13/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DISCUSSED SCHEDULING AND PROGRESS |
|
07/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PSBR (ALL) AND TSBR 2) OK TO USE FLEX CONDUIT TO TRANSITION DUE TO SPACE |
|
07/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO MAINS HL9W, HL8E,P8EA,HL8W,P8UA,HL7E,P7EA,H67W,P7WA,HL6E,P6EA,HL6W,HL5E,P5EA,HL5W,P5WA 2) OK TRANSFORMER T8E,T8W,T7E,T7W,T6E,T6W,T5E,T5W 3) OK REPAIRS BUSS DUCTS 1,2,6 & 7 4) PANEL P8WA MISSING PARTS 5) ADD ADDITIONAL BUSS DUCT SUPPPORTS AT COUPLINGS AS DISCUSSED 6) MAINTAIN ILLUMINATION AT EQUIPMENT |
|
07/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK "HSBR" PANEL 2) OK STAIRWELL 210,110,B1,B2 & B3 |
|
07/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CANS HALL CEILING ON 4TH FLOOR WEST |
|
07/06/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DISCUSSED WORKING SPACE PERM 110.26 AT COOLING TOWERS WITH TODD OF ROSENIDIN AND RICK BENJAMIN OF RYAN, RICK WAS GOINTG TO ADD A PLATFORM AT CT2 AND MOVE COPPER PIPES AT OT1 & 3 |
|
07/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK BUSS DUCT 3 TO ENERGIZE AFTER CORRECTIONS 2) OK PANEL ELEV AND XFMR ELEV 3) SUPPORT BUSS DUCTS AT "ATF'S" AS DISCUSSED 4) DO NOT FOLD CONDUCTOR AT XFMR LUGS |
|
06/30/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CONNECTIONS FOR AND AT "DPELEV" 2) OK BONDING AT ATF |
|
06/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH STRAPPING AND SUPPORT BUSS DUCT AT 1 WEST 2) MEET WITH ELEVATOR INSPECTOR TO DETERMINE JURISDICATION OF ROOM |
|
06/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK HARD LIDS 107,108 & 115 |
|
06/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
06/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK STAIRWELL (1) 108-908 2) OK STAIRWELL (3) 120-220 3) OK HARD LIDS 501,601,701 AND 801 EXCEPT AS NOTED 4) MISSING EM LIGHTS 501 |
|
06/24/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL 4 PARAPET CHANGES OK | |
06/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) MAINTAIN WORKING CLEARENCE AT COOLING TOWERS 1,2,3 2) NOTE: ELEVATORS FOR INTERIOR ARE ON TEMP POWER |
|
06/22/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection : 1) GENERAL WALK THRU AND ANSWER QUESTIONS |
|
06/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 2 CORE REDO AFTER CORRECTIONS 2) NEED BANG PLATE PROTECTION FOR FLEX AND M/C CABLE |
|
06/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) STAIR WELL #1 LOOSE FITTINGS 2) SUPPORT CONDUIT ON HORIZONTALS |
|
06/15/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NOTE: AT MULTI POLE DUCT TRANSITIONS MAY NEED ADDITIONAL TOP SUPPORTS |
|
06/14/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) NOTE: BUSS DUCTS HAVE BEEN WATER DAMAGED-BEING REMOVED AND SENT BACK TO FACTORY FOR EVALUATION AND REPAIR |
|
06/13/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK HL4E, H4E, HL5E, HL6E, HL7E, H7E, HL8E, H8E, HL9E AND H9E 2) AIR HANDLERS: TIGHTEN LOOSE FITTINGS, PROPERLY STRAP CONDUIT TO FLOOR AND WALLS, REDUCING WASHERS NOT INSTALLED CORRECTLY, UNDERSIZED WIRE NUTS AND SEAL TIGHT NOT FULLY INSTALLED INTO FITTING 2) DO NOT STACK LUGS IN TRANSFORMER |
|
06/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK BUSS SUPPORTS ON FLOOR 9 EAST AND WEST ELECT ROOMS 2) OK CHILLER AND CEILING TOWER #1 3) TIGHTEN AND SECURE 4" TO CHILLER 4) NEED ACCESS TO BUSS DUCTS 5 & 9 ON FLOOR 2 |
|
06/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) TIGHTEN LOOSE FITTINGS 209 SOUTH AND TIGHTEN CARD READER BOX 2)_ CLIMATIC FOR SUN MECH: TIGHTEN ALL LOOSE FITTINGS AND STRAP RACEWAYS TO FLOOR-ALL LEVELS |
|
06/06/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS 102,103,104,105,106,107, 202, 302, 402, ATRIUM WALL AT 2ND FLOOR FOR LIGHTS 1. MECHANICAL ROOM 108 COVERED WITHOUT INSPECTION 2. STRAP CONDUITS DOWN FROM CEILING AT VESTABULE FOR ELEVATORS FLOOR 1-9 |
|
06/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FILL UNUSED OPEININGS IN TOP OF SES 2) SUPPORT BD #1 ABOVE SES 3) FINISH SUPPORTS ON HORIZONTALS BBD 1,2,3,6,7 & 5 4) NEED VERTICAL SUPPORTS ELECTRIC ROOM 1E, 1W, 3E AND 9W 5) SUPPORT COUPLINGS AT WALL DOWN TO ELECTRIC ROOM 1W 6) SUPPORT DUCT UNDER DPR 7) NEED PLUG CAP ON HORIZONTAL RUN 1ST FLOOR 8) ADD STABILIZATION WASHERS UNDER FLOOR 9E 9) NEED CENTER SUPPORT VERTICAL 2W 10) MAINTAIN DEDICATED SPACE BELOW SB1E AND UPS1E 11) OK BUSS TO PANEL TAPS DPR, DSCPB, HSB1W 12) OK BUSS DUCTS 4 & 8 FROM SES TO CENTRAL PLANT 13) OK 1, 2, 6 & 7 HORIZONTAL ON 1ST FLOOR BUSS DUCTS 14) OK 1, 2, 6 & 7 VERTICAL FLOORS 1 TO 9 BUSS DUCTS 15) OK BUSS PLUGS #4E, HL4E, H4W, HL4W, H5E, HL5E, HL5W, H5W, H6E, HL6E, H6W, HL6W, H7E, HL7E, H7W, HL7W, H8E, HL8E, H8W, HL8W, HL9E, HL9W AND H9W |
|
06/03/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VERIFY WITH ENGINEER FOR METHOD OF GROUNDING ELECTRODE TAPS 250.30 (A) |
|
06/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DISCUSSED GROUNDING SITUATIONS-GROUNDING ELECTRODE CONDUCTOR AND GROUND BARS 2) NEED ACCESS TO JUNCTION BOXES ABOVE HARD LIDS |
|
06/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RECEIVED BREAKER TEST REPORTS-NOT ALL HAVE GFI TEST REPORTS |
|
05/31/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 502, 602, 702, 802, 902 | |
05/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 3 CANS OUTSIDE 114 2) SUPPORT 2 1/2" EMT WITHIN 3' OF SES |
|
05/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 3 CANS OUTSIDE 114 2) SUPPORT 2 1/2" EMT WITHIN 3' OF SES |
|
05/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 4" EMT COMM1 (103) TO COMM2 (112) 2) ANSWER QUESTIONS FOR ROOF |
|
05/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CRANE HOLD GROUND LEVEL EMT, BOX AND SLEEVES 2) OK FEEDER CONDUITS "PG", "HGB", "HMPOP" AND "PMPOP" 3) OK 8-4" EMT "MPOP" TO COMM 1 (103) 4) TIGHTEN LOOSE FITTINGS 4" EMT COMM1 (103) TO COMM2 (112) 5) TIGHTEN STRUT RAIL SUPPORTS |
|
05/19/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/18/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ANY AND ALL MODIFICATION TO SWITCH GEAR NEED NTRL EVALULATION |
|
05/17/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE CONDUCTORS TO BE PER 230.7, 408.3 AND 352.46 |
|
05/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK UNDER FLOOR 612 2) OK 4 BOXES AND STUBS SOUTHSIDE OF GARAGE LIGHTS 3) ANSWERED QUESTIONS REGARDING FIRE PUMP |
|
05/13/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
05/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS R02 & R03 2) PROTECT CONDUCTORS AT RACEWAYS 300.4 & 408.3 3) PROTECT TENT AT TRANSITION BLOCK TO CONDUITS LEVEL 1 & 2 MAINTENANCE ROOM |
|
05/10/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
05/09/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ROOF: 1) PROTECT SEAL TITE FROM SHARP METAL EDGE AH-10.1, 10.2 AND 10.3 2) TIGHTEN LOOSE FITTINGS AH-10.3 3) NO MORE THAN 360 DEGREE IN CONDUIT RUNS 9TH FLOOR: 1) OK RECESSED CANS EAST TERRANCE |
|
05/06/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/05/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK HARD LIDS 906, 907, 917 & 918 |
|
05/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/03/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ON CORE 203-205, 208, 211-213 OK LIDS 206, 207 OK SOFFIT IN RM 340 OK WALLS 311 2ND FLOOR 1) PROTECT M/C INSIDE OF CHANNEL STUDS 2) SECURE CONDUIT BETWEEN BATHROOMS |
|
05/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO CLEAR TO MAIN BREAKERS ONLY A & B OK HAND LIDS 807, 806 1)DONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT 2) DO NOT ENERGIZE FIRE PUMP CONTROLER OR SES "MSE" 3)PROVIDE PROTECTION FOR CONDUITS AT SES "A" 4) NEED GFI TEST RECIEVED MEGER TEST SHEETS & TORQUE SHEETS |
|
04/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | 3RD FLOOR ABOVE CIEL DONE LAST WEEK | |
04/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FOR SWITCH GEAR: WILL NEED LETTER VERIFYING TORQE OF EQUIPMENT, ILLUMIMATION, LOCK OUT/TAG OUT PROCEDURES, SECURED IN PLACE * PLEASE VERIFY FAULT CRRENT AT 4000A MAINS A & B |
|
04/26/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 2ND FLOOR BATHROOMS COVERED WITHOUT INSPECTION 2) 3RD FLOOR BATHROOMS NOT FINISHED 3) OK 1ST FLOOR CANNS LOBBY ENTRANCE 4) OK 1ST & 4TH FLOOR BOXES, FLEX CONDUIT AND EMT FOR CATHEDRAL LIGHTING 5) 300.3 (C) (2) (A) & (B) 6) CONDUITS IN SHAFTS FOR FIRE ALARM CONTROL WIRING IS INSTALLED ONLY TO MINIMUM CODE ADDITONAL SUPPORTS MAYBE NECESSARY |
|
04/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CIELINGS IN FLOOR 2 + 3 BATH ROOMS NOT READY 2. VERIFING SUPPORT OF RACEWAYS W SHAFTS FOR FIRE CONTROL CABLES |
|
04/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
04/18/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/14/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS R04 AND CORE EXTERIOR WALLS 2) OK EAST WALL ROOF FOR WALL LIGHTS |
|
04/05/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 610, 611, 613, 608, EAST AND WEST SHAFT 6TH 2) FINISH 602 |
|
03/31/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO WORK PROGRESS |
|
03/30/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 513 WALLS |
|
03/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ROOMS 511 AND STAIRWELL 2) OK RUNS FOR TI ON BATHROOM WALL-CONDUIT UP WALL 3) OK INSIDE BOTH SHAFTS ON #5 4) FINISH 502 & 513 5) FINISH 602, 611, 613, STAIRWELL AND TI STUBS |
|
03/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* LEVEL B-2 FILL UNUSED OPENINGS IN FIXTURES 110.12 |
|
03/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PULL BOXES TO BE PER 314.28 LOWER LEVELS 2) VERIFY 360 DEGREE OF RUN THRU CEMENT AND CONDUITS |
|
03/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS ROOMS #403, 405, 503, 505, 603, 605, 703, 705, 803, 805 AND 905 |
|
03/17/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | FLOORS 4 THROUGH 9 OK TO COVER ELECTRICAL ROOM WALLS BY ELEVATOR. | |
03/17/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS ROOMS 202-205, 302-305 2) OK AS MARKED WALLS 208,211,308 & 311 |
|
03/15/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
03/14/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS 912 & 812 |
|
03/11/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
03/10/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) TIGHTEN LOOSE FITTINGS (812) |
|
03/09/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 6,7,8 & 9 FLOORS TO POUR STUBS 2) OK WALLS 512,612,712 & 812 |
|
03/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SEPERATE EM CIRCUIT AND REGULAR CIRCUIT FOR LIGHTING IN BOXES, ALSO NOTE IF MORE THAN 300V BETWEEN DEVICES 2) DO NOT POUR EMT ENCASEMENTS UNTIL INSPECTED 3) OK WALLS #202,203,204,212,304,312,404,412,606,607,706 AND 707 4) OK FLOOR STUBS: FLOORS 2-7 |
|
03/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SECURE CONDUIT IN WALLS 2) PROTECT FLEX IN STUD CHANNELS |
|
03/03/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
03/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALL 406, 407, 506 AND 507 |
|
03/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) JUNCTION BOX TO BE ACCESSIBLE 314.20 WILL APPLY 2) OK WALLS 106, 107, 206, 207, 306 AND 307 |
|
02/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL 4 EAST UNDER CONST. | |
02/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL 4 SW CONDUIT AND OUTLETS OK | |
02/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/08/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK DECK 3 SOUTH + EAST OK FIRE, COMM + CAMERA FINISH POWER + LIGHTING ROOF WEST |
|
02/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ELECTRICAL INSIDE COLUMNS AND SHEARWALLS OK TO LEVEL 4 S AND SW SECTIONS. | |
02/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
02/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ROOF EAST SIDE OK TO COVER CONDUITS AND OUTLETS | |
02/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROOF DECK NORTH EAST ENT, BOXES & GROUNDS |
|
01/31/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL 9 WEST AND RAMP 2-3 OK TO COVER CONDUITS AND OUTLETS | |
01/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FIRE ALARM, SECURITY + CAMERA BOXES + ENT 1. FINISH LIGHTING POWER + EMERGENCY |
|
01/18/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL 9 NE OK TO COVER. LEVEL 2 SW OK TO COVER. COLS & SHEARWALLS LEVEL 8 AND RAMP 1-2 OK TO COVER. | |
01/13/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL 8 WEST SIDE IN-SLAB CONDUITS AND OUTLETS OK TO COVER | |
01/13/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 8TH DECK NORTHWEST BOXES, EMT, BUSS DUCT SLEEVES AND PASS THRU SLEEVES |
|
01/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
01/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ELECTRICAL OUTLETS AND CONDUITS IN RAMP FROM LEVEL 1 - 2 OK. | |
01/06/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | CONDUITS AND OUTLETS IN SLAB LEVEL 8 EAST OK. ONGOING PLACEMENT OF OUTLETS AND CONDUITS IN MASONRY AT PLAZA LEVEL ARE OK |
|
01/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL 7 WEST IN SLAB ELECTRICAL OUTLETS AND CONDUIT OK | |
12/30/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | NEED TO RELOCATE OUTLETS AND CONDUITS IN BEAM LINE 15 FROM A-C. CANNOT HAVE PLASTIC IN CRUSH ZONES OF TENDONS. CONDUIT BURNING DECK AT J14 AND TOO CLOSE TO TOP OF SLAB AT I13. | |
12/27/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL 7 NE OK TO COVER CABLES, CONDUITS AND OUTLETS IN SLAB | |
12/23/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL 6 NW OK TO COVER CABLES AN CONDUITS IN FLOOR SLAB. | |
12/20/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | CENTRAL AREA OF SOUTH PLAZA LEVEL CONDUITS AND CABLES OK | |
12/17/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
12/16/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK EMT AND BOXES 6 DECK NORTHEAST |
|
12/07/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK BOXES AND EMT 2) DECK 5 NORTHEAST |
|
12/01/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
11/30/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH RACKS AND TIES TO SES "B" 2) SES "B" PULL BOX IS 48" WIDE-314.28 (A) (2) DUE TO DESIGN THIS WILL BE ALLOWED |
|
11/29/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) LOOKED AT PULL SECTIONS (?) |
|
11/23/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | NE LEVEL 4 OK FOR ELECTRICAL IN SLAB | |
11/23/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | CABLES AND CONDUITS IN COLS LEVEL 4 NE OK | |
11/23/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 4 DECK NORTHEAST EXCEPT EDGES |
|
11/19/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/17/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/17/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | CONDUITS AND OUTLETS INSIDE FLOOR OK TO COVER LEVEL 3 NW | |
11/12/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | CABLES AND CONDUITS IN COLS AT NE LEVEL 3 OK | |
11/11/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | NE LEVEL 3 CONDUITS AND OUTLETS IN SLAB OK. OUTLETS ADDED FOR LIGHTING THAT ARE NOT YET ON APPROVED PLAN BUT WILL BE ON TI PLAN IN AREA 1-4/H-J | |
11/10/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | CONDUITS AND OUTLETS IN CONCRETE RAMP FROM B1 TO PLAZA LEVEL OK | |
11/08/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | CONDUITS AND CABLES INSIDE COLS AND SHEARWALLS SE LEVEL B1 OK CONDUITS AND CABLES INSIDE COLUMNS NW LEVEL 2 OK |
|
11/05/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/04/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
11/04/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) MET WITH CONTRACTOR, ELECTRICIAN AND GARRETT, TO DISCUSS COMM ROOM RACEWAYS-EMT WILL BE STUBBED UP AND WE WILL WAIT ON ENGINEER |
|
11/03/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/02/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
11/02/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | CABLES OK IN SHEARWALLS NE LEVEL 2 OK | |
11/01/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | CABLES AND CONDUITS INSIDE COLUMNS AND SHEAR WALLS NW LEVEL B1 OK CABLES AND CONDUITS INSIDE COLUMNS NE LEVEL 2 OK |
|
10/30/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/29/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | NE LEVEL 2 OK TO PLACE FLOOR SLAB. CONDUITS AND OUTLETS OK. | |
10/29/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) SECURE AND STRAP FOR SNORKEL 90 DEGREE AND BLOCKOUTS LEVEL 2 ? NORTH EAST |
|
10/28/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | OK LEVEL B1 SOUTH A-E | |
10/26/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK B-1 TO B-2 RAMP SOUTHEAST 2) BOXES WITH WRONG KO PUNCHED OUT TO BE REPLACED- DUCT TAPE NOT AN APPROVED METHOD |
|
10/26/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | COLUMN AND SHEARWALL RUNS NORTH SIDE LEVEL 1 APPROVED. | |
10/19/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | SOUTH EAST AREA OF LEVEL B2 OK FOR IN SLAB | |
10/19/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | 1) PLAZA LEVEL NW- OK TO COVER ELEC IN SLAB 2) COLS AND SHEAR WALLS PLAZA LEVEL NE CONDUITS AND BARE CONDUCTORS OK. OK TO COVER 3) CONDUCTORS OK IN LEVEL B2 SW COLUMNS |
|
10/15/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK NORTHEAST DECK B1-B2 ENT, BOXES, PVC FOR POWER, SECURITY, CO-2, + DATA |
|
10/13/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK GENERATOR AREA PLAZA 2) SUPPORT EMT PER CODE 3) FINISH RUNS |
|
10/12/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK SOUTH WST EMT, BOXES, SECURITY,POWER AND DATA-DECK B-3/B-2 |
|
10/05/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK COLUMNS AND SHEARWALL BOXES & PVC B-1 NORTH WEST |
|
10/04/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/02/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/01/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
09/30/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK RECEPTS AND LIGHTS IN COLUMN WALLS STAIR #2 ON B-1 |
|
09/29/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | OK TO CLOSE AND PLACE COLUMNS AND SHEAR WALLS LEVEL B1 @ E-J/3-11 | |
09/27/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IN SLAB CONDUITS LEVEL B1 AREA 3-11/E-J OK | |
09/27/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) OK B-1 DECK, CONDUITS, BOXES, SECURITY AND FIRE ALARM NORTH EAST CORNER |
|
09/27/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 2 LIEBERT UNITS IN UPS ROOM 2) OK CONDUIT AND BOXES FLOOR 2ND, EAST OF 'D' SOUTH OF CORE AND ROOMS 254 AND 255 3) FILL UNUSED OPENING FA BOX 6TH FLOOR 4) STRAP FIRE CONDUITS CORRECTLY 4TH AND 5TH FLOOR 5) JUNCTION BOXES TO BE ACCESSIBLE 5TH FLOOR 6) SEPERATED FLEX CONNECTOR 5TH FLOOR 7) SUPPORT FA BOXES OVER ONE EXTENTION ALL FLOORS |
|
09/23/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | OK LEVEL B2 AREA A-E/3-11 FOR IN SLAB ELECTRICAL | |
09/22/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK POWER RUNS B2 NEW DECK |
|
09/21/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) MAINTAIN CLEARANCES WITH POST TENSION CABLES |
|
09/17/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK NORTH EAST IN B-2 DECK 2) PVC CONDUITS, BOX FOR LIGHTS, FIRE ALARM AND SECURITY |