Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM01795
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2011 | ELECTRIC - INTERMEDIATE | Approved | SEE BUILD-OUT ACTIVITY T10CM03478 FOR FINAL INSPECTION INFORMATION | |
10/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) TIGHTEN LOOSE FITTINGS AT TIBER FLOW UFD'S 2) WHERE IS MASTER GFCI FOR BATHROOMS |
|
10/06/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO RFD CONTROLS LINE SIDE B1, B2, B3 |
|
09/30/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DISCONNECTING MEANS NEEDED FOR ROLL UP DOOR MOTORS |
|
09/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PANELS PSBMPOP, HMPOP, PMPOP, H4W, H4E, S5E, H5W,H6E, H6W, P3WA, P3WB, T3W, P3EA AND P3EB 2) ADDRESS LABELING ISSUES WITH ONE LINE AND EAST ELECTRIC PANEL A & B'S |
|
09/23/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROTECT CONDUCTERS AT BOXES FROM SHARP METAL EDGES 2) WILL NEED ARC SHEILDS 314.2 3) NEED JUNCTION BOX ACCESS LEVELS B1,B2, B3 ELEVATOR LOBBIES 4) FILL UNUSED BOX OPENINGS 5) VERIFY CONDUCTER DEPATING 310.15 6) BOXES CUT ON ROUNDS 314.2 7) LABEL CONDENSING UNIT DISCONNECTS 8) IDENTIFY FIRE ALARM BOXES 760.10 |
|
09/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SEAL TOP OF FIRE PUMP CONTROLLER AND JOCKEY PUM CONTROLLER FOR WET LOCATION |
|
09/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
09/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |
Showing 1 to 10 of 200 entries