Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T10CM01795
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2011 | ELECTRIC - UNDERGROUND | Approved | ||
09/16/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
05/13/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
02/08/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
02/08/2011 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
01/31/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 3RD DECK SOUTHWEST 2) EMT & BOXES DATA AND LIGHTING 3) LOOSE FITTINGS IN WALLS 4) VERIFY METAL ADJUSTABLE RINGS |
|
01/24/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) NOTE: NUMEROUS BREAKAGE IN STUB UPS INTO FLOORS ABOVE 2) VERIFY RUNNING LIGHTING CONDUCTOR HORIZONTAL IN SLAB 3) DATA BOND CONDUCTOR CUT |
|
01/20/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK FIRE ALARM, SECURITY + CAMERA BOXES + ENT 1. FINISH LIGHTING POWER + EMERGENCY |
|
01/06/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
12/29/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) PVC AND EMT TO BE MIDDLE 1/3 OF SLAB 2) OK PLAZA EMT, PVC FOR LIGHTS AND DATA 3) OK GENERATOR 2" TO FIRE PUMP 4) OK POWER FOR PARKING CONTROL BOOTHS |
|
12/16/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
12/13/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 5TH DECK NORTHWEST: 1) VERIFY LIGHTING CONDUCTOR TRAVELING HORIZONTAL THRU DECK 2) OK EMT AND BOXES |
|
11/23/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
11/19/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 4" PVC FOR MAN LIFT |
|
11/17/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) VERIFY SNORKLE 90 DEGREE AND BOXES WITHIN CABLE PULL ZONE EAST END 2) OK 3RD DECK NORTH WEST |
|
11/05/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK DECK LEVEL 2 NORTH EAST 2) EXCEPT COMM STUBS 3) OK GROUNDING DATA TO DATA #2 BARE 4) OK GROUNDING 3/0 TO M.P.O.P. ROOM |
|
11/04/2010 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) MET WITH CONTRACTOR, ELECTRICIANS AND GARRETT TO DISCUSS COMM ROOM RACEWAYS-EMT WILL BE STUBED UP AND WILL WAIT ON ENGINEER AND OWNERS APPROVAL FOR INSTALLATION METHOD |
|
11/04/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK DECK B-1 SOUTH EAST |
|
11/03/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) SUPPORT EMT WITHIN 12" OF FITTINGS |
|
11/02/2010 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) STILL PULLING EMT-FINISH ELECTRIC |
|
10/30/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
10/29/2010 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
10/26/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
10/15/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
10/13/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
10/12/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
10/02/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK POWER, LIGHTS, FIRE ALARM, SECURITY IN DECK B-1 NORTH WEST 2) CONTRACTOR HAS SWITCHED TO EMT AND PLASTIC BOXES 3) NEW MATERIAL BARRIES LISTING MARKINGS 4) LEE RAY TO HANDLE AFTER HOURS INSPECTION FEES |
|
09/27/2010 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
09/27/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
09/22/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
09/21/2010 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
09/17/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* |