Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T10CM01795
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2011 | ELECTRIC - UNDERGROUND | Approved | ||
| 09/16/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 05/13/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 02/08/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 02/08/2011 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
| 01/31/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 3RD DECK SOUTHWEST 2) EMT & BOXES DATA AND LIGHTING 3) LOOSE FITTINGS IN WALLS 4) VERIFY METAL ADJUSTABLE RINGS |
|
| 01/24/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) NOTE: NUMEROUS BREAKAGE IN STUB UPS INTO FLOORS ABOVE 2) VERIFY RUNNING LIGHTING CONDUCTOR HORIZONTAL IN SLAB 3) DATA BOND CONDUCTOR CUT |
|
| 01/20/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK FIRE ALARM, SECURITY + CAMERA BOXES + ENT 1. FINISH LIGHTING POWER + EMERGENCY |
|
| 01/06/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 12/29/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) PVC AND EMT TO BE MIDDLE 1/3 OF SLAB 2) OK PLAZA EMT, PVC FOR LIGHTS AND DATA 3) OK GENERATOR 2" TO FIRE PUMP 4) OK POWER FOR PARKING CONTROL BOOTHS |
|
| 12/16/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 12/13/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 5TH DECK NORTHWEST: 1) VERIFY LIGHTING CONDUCTOR TRAVELING HORIZONTAL THRU DECK 2) OK EMT AND BOXES |
|
| 11/23/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 11/19/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 4" PVC FOR MAN LIFT |
|
| 11/17/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) VERIFY SNORKLE 90 DEGREE AND BOXES WITHIN CABLE PULL ZONE EAST END 2) OK 3RD DECK NORTH WEST |
|
| 11/05/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK DECK LEVEL 2 NORTH EAST 2) EXCEPT COMM STUBS 3) OK GROUNDING DATA TO DATA #2 BARE 4) OK GROUNDING 3/0 TO M.P.O.P. ROOM |
|
| 11/04/2010 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) MET WITH CONTRACTOR, ELECTRICIANS AND GARRETT TO DISCUSS COMM ROOM RACEWAYS-EMT WILL BE STUBED UP AND WILL WAIT ON ENGINEER AND OWNERS APPROVAL FOR INSTALLATION METHOD |
|
| 11/04/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK DECK B-1 SOUTH EAST |
|
| 11/03/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) SUPPORT EMT WITHIN 12" OF FITTINGS |
|
| 11/02/2010 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) STILL PULLING EMT-FINISH ELECTRIC |
|
| 10/30/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 10/29/2010 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
| 10/26/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 10/15/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 10/13/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 10/12/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 10/02/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK POWER, LIGHTS, FIRE ALARM, SECURITY IN DECK B-1 NORTH WEST 2) CONTRACTOR HAS SWITCHED TO EMT AND PLASTIC BOXES 3) NEW MATERIAL BARRIES LISTING MARKINGS 4) LEE RAY TO HANDLE AFTER HOURS INSPECTION FEES |
|
| 09/27/2010 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
| 09/27/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 09/22/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 09/21/2010 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
| 09/17/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* |