Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/24/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) NOTES DATED 2/9/11 HAVE BEEN ADDRESSED, DRYER BEING INSTALLED IS A WHIRLPOOL MOEL WED48COX, THE CHART FOR THIS UNIT EXCEEDS DRYER DUCT LENGTH, OK TO INSTALL THIS UNIT. LIGHT AT FC-7 HAS BEEN RELOCATED 2) BALANCE REPORT INDICATED FC-7 IS LOW IN AIR FLOW APPROX 25 PERCENT 3) SEE BLDG INSPECTOR FOR TEMP C OF O, NO LIFE SAFETY ISSUES OBSERVED |
|
| 06/22/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |