Permit: T10CM01765

Parcel: 110162860

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM01765

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/29/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/24/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) NOTES DATED 2/9/11 HAVE BEEN ADDRESSED, DRYER BEING INSTALLED IS A WHIRLPOOL MOEL WED48COX, THE CHART FOR THIS UNIT EXCEEDS DRYER DUCT LENGTH, OK TO INSTALL THIS UNIT. LIGHT AT FC-7 HAS BEEN RELOCATED
2) BALANCE REPORT INDICATED FC-7 IS LOW IN AIR FLOW APPROX 25 PERCENT
3) SEE BLDG INSPECTOR FOR TEMP C OF O, NO LIFE SAFETY ISSUES OBSERVED
06/22/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*