Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
Permit Number - T10CM01713
Inspection Description - PLUMBING - GAS PRESS TEST FNL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2010 | PLUMBING - GAS PRESS TEST FNL | Approved | IVRS - Inspection :* | |
| 06/29/2010 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* 1) FLUE EXHAUST NOT PROPERLY INSTALLED, PROVIDE PROPER MATERIAL, CONTINUE PIPING THRU ROOF 2) PROVIDE SECONDARY DRAIN ON COIL 3) COMPLETE LINE SET INSULATION 4) CLEAN UP ALL BARE WIRES AND BOXES WITHOUT COVER PLATES, NO EXPOSED WIRING 5) COMPLETE W/H FLUE PIPING |