Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/22/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROTECT M/C CABLE ON INSIDE OF STUD CHANELS 2) USE APPROVED M/C STRAPS 3) PROPERLY SUPPORT M/C CABLE 6' INTERVALS 330.17 4) IDENTIFY UNGROUNDED SWITCH ? 200.7 |