Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/21/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEED OCCUPANCY SENSORS PER PLANS 2) SECURE FIXTURES TO GRID 410.16 3) FINISH PANEL SCHEDULE 408.4 AND NOTE ON PLANS |
|
| 08/19/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CEILING HAS OPEN BOXES, PIPES TO BE STRAPPED 3' FROM BOX, LOW VOLTAGE STRAPPED OFF T-BAR CEILING 2) SERVICE HAS GROUNDING AND NEUTRAL, BUT SUB PANEL DOES NOT 3) SUB PANEL ON TOP OF SUB PANEL REMOVE AND RELOCATE TALK TO ENGINEER 4) OFFICE, BREAKROOM AND PREP ROOM WALLS OK |