Permit: T10CM01690

Parcel: 13317062G

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/15/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL
12/10/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) AS PER PLANS, IMC SECTION 606 DOES NOT REQUIRE DUCT SMOKE DETECTORS IN 2000 CFM UNITS
2) SECURE MINI SPLIT CONDENSOR. PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX AND REMOVE DUCT TAPE
3) PROVIDE AIR BALANCE REPORT