Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/16/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL OPEN ENDS OF SPARE RACEWAYS INTO PANELS 2) EXPLAIN RECEPT ABOVE CEILING 3) NEED TIE WIRES TO RECESSED FIXTURES 4) PROPERLY STRAP/SECURE MC CABLE DOWN HALLS 5) STRAP MC CABLE WITHIN 12" OF BOXES |