Permit: T10CM01648

Parcel: 136336020


Addresses:

3264 S EASTVIEW AV

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/18/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RELOCATE LINE SET FROM BLOCKING REMOVAL OF WATER HEATER
2) FURNACE/AIR HANDLER IS ALSO BLOCKING REMOVAL OF WATER HEATER
3) PROVIDE A BUSHING IN KNOCKOUT OF FAN COIL TO PROTECT PUMP CORD
4) MARK UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED
5) PROVIDE A NEUTRAL WIRE FOR THE SERVICE RECEPT