Permit: T10CM01647

Parcel: 11451216G

Inspection Status: Denied

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T10CM01647

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Denied

Date Description Inspector Results Comments
07/26/2010 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE ENTIRE STORE WAS REDUCTED
2) PROVIDE A COMPLETE MECHANICAL PLAN WITH ALL NEW DUCT SIZES AND CFM REQUIREMENTS
3) SUPPORT DIFFUSER TO STRUCTURE
4) DO NOT USE PRODUCT STRAPS TO SUPPORT ANY DUCTS
5) STRAP ALL FLEX UP OFF OF LIGHTS
6) FOR FINAL PROVIDE A COMPLETE AIR BALANCE REPORT
7) TERMINATE CONDENSATE TO AN APPROVED LOCATION
8) PAINT EXPOSED ARMAFLEX WITH PROTECTIVE COATING