Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T10CM01647
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2010 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE ENTIRE STORE WAS REDUCTED 2) PROVIDE A COMPLETE MECHANICAL PLAN WITH ALL NEW DUCT SIZES AND CFM REQUIREMENTS 3) SUPPORT DIFFUSER TO STRUCTURE 4) DO NOT USE PRODUCT STRAPS TO SUPPORT ANY DUCTS 5) STRAP ALL FLEX UP OFF OF LIGHTS 6) FOR FINAL PROVIDE A COMPLETE AIR BALANCE REPORT 7) TERMINATE CONDENSATE TO AN APPROVED LOCATION 8) PAINT EXPOSED ARMAFLEX WITH PROTECTIVE COATING |