Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
Permit Number - T10CM01647
Inspection Description - PLUMBING - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/28/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE NOTES 2, 9 AND 10, ALSO YOU HAVE A LEAK 2) SUPPORT ICE MAKER DRAIN AND PROVIDE AIR GAP 3) SEE UPC CODE SECTION 602.2 REQUIRING EACH CONNECTION TO BE SEPERATELY PROTECTED 4) YOU WILL NEED TO RECERT RP |
|
07/26/2010 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) LETTERS RECEIEVED OK 2) SUPPORT LAV MIXING VALVES AND CONNECT CW TO LAVS 3) COMPLETE REMAINING ITEMS |
|
07/23/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED STAMPED LETTER FOR ALL CHANGES 2) WATER HEATER REQUIRES A VACUUM RELIEF VALVE AND SUPPORT EXP TANK 3) LEAK ON SINK STRAINERS 4) SANITARY TEES ARE NOT ALLOWED TO BE INSTALLED HORIZONTALLY ON DRAIN PIPING 5) SWEEPS REQUIRED AT VERTICAL TO HORIZONTAL 6) CLEANOUT PLUGS SHALL BE LISTED TO RECEIVE THE SCREW 7) REPLACE ALL DAMAGED PLUGS 8) NEW LAVS REQUIRE ANTI SLAB PROTECTION 9) PROVIDE BACKFLOW PROTECTION PER LOW HAZARD, NON CARBONATED BEVERAGES AND ICE 10) CONNECT UP STREAM OF CARBONATED SUPPLY 11) INSTALL DRAIN PIPING IN A WORKMANSHIP LIKE MANOR IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS |