Permit: T10CM01647

Parcel: 11451216G

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Permit Number - T10CM01647

Inspection Description - PLUMBING - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
07/28/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) COMPLETE NOTES 2, 9 AND 10, ALSO YOU HAVE A LEAK
2) SUPPORT ICE MAKER DRAIN AND PROVIDE AIR GAP
3) SEE UPC CODE SECTION 602.2 REQUIRING EACH CONNECTION TO BE SEPERATELY PROTECTED
4) YOU WILL NEED TO RECERT RP
07/26/2010 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) LETTERS RECEIEVED OK
2) SUPPORT LAV MIXING VALVES AND CONNECT CW TO LAVS
3) COMPLETE REMAINING ITEMS
07/23/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NEED STAMPED LETTER FOR ALL CHANGES
2) WATER HEATER REQUIRES A VACUUM RELIEF VALVE AND SUPPORT EXP TANK
3) LEAK ON SINK STRAINERS
4) SANITARY TEES ARE NOT ALLOWED TO BE INSTALLED HORIZONTALLY ON DRAIN PIPING
5) SWEEPS REQUIRED AT VERTICAL TO HORIZONTAL
6) CLEANOUT PLUGS SHALL BE LISTED TO RECEIVE THE SCREW
7) REPLACE ALL DAMAGED PLUGS
8) NEW LAVS REQUIRE ANTI SLAB PROTECTION
9) PROVIDE BACKFLOW PROTECTION PER LOW HAZARD, NON CARBONATED BEVERAGES AND ICE
10) CONNECT UP STREAM OF CARBONATED SUPPLY
11) INSTALL DRAIN PIPING IN A WORKMANSHIP LIKE MANOR IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS