Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/16/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SEAL ROOF FLASHINGS W/ TAR (SEE PLUMBERS INSTALLATION) SEAL + PROTECT PIPE INSULATION PER MANUFACTURERS RECOMMENDATIONS SUPPORT ENCLOSURE ROOF IN ALL FOUR SIDES MAKE IT WEATHER TIGHT AND SEAL EXPOSED EDGERS SUPPORT PLASTIC PAD |
|
| 08/18/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE TAPE FROM VENT CONNECTOR, SECURE WITH SCREWS 2) PROVIDE THE MINIMUM CLEARANCE REQUIRED FROM B VENT AT ROOF PENETRATION 3) COMPLETE PETITION OF APPEAL FORM FOR RELIEF VALVE TERMINATION 4) EXTERIOR WATER HEATER REQUIRES PROTECTION FROM WEATHER 5) PROVIDE THE PRODUCT LISTING AND INSTRUCTIONS FOR PLASTIC SUPPORT PAD 6) SEAL ALL JOINTS IN PIPE INSULATION AND APPLY PROTECTIVE COATING 7) GFI OUTLET REQUIRED OUTDOORS NOTE: NEW FURNACE REQUIRES A PERMIT AND INSPECTION. VENT IS NOT PROPERLY CONNECTED |
|
| 07/27/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER VENT NOT CONNECTED 2) GAS TURNED OFF, PROVIDE LISTED VENT CONNECTORS INSTALLED IN A WORKMANSHIP LIKE MANOR 3) NEW GAS WATER HEATER REQUIRES A NEW FLEX AND SEDIMENT TRAP 4) ALL PLUMBING PIPES, PARTS AND APPLIANCES SHALL BE INSTALLED PER THEIR LISTING REQUIREMENTS 5) INSPECTION STOPPED |