Permit: T10CM01619

Parcel: 106071950


Addresses:

934 W NAVAJO ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
11/12/2010 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/16/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEAL ROOF FLASHINGS W/ TAR (SEE PLUMBERS INSTALLATION) SEAL + PROTECT PIPE INSULATION PER MANUFACTURERS RECOMMENDATIONS SUPPORT ENCLOSURE ROOF IN ALL FOUR SIDES MAKE IT WEATHER TIGHT AND SEAL EXPOSED EDGERS SUPPORT PLASTIC PAD
08/18/2010 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE TAPE FROM VENT CONNECTOR, SECURE WITH SCREWS
2) PROVIDE THE MINIMUM CLEARANCE REQUIRED FROM B VENT AT ROOF PENETRATION
3) COMPLETE PETITION OF APPEAL FORM FOR RELIEF VALVE TERMINATION
4) EXTERIOR WATER HEATER REQUIRES PROTECTION FROM WEATHER
5) PROVIDE THE PRODUCT LISTING AND INSTRUCTIONS FOR PLASTIC SUPPORT PAD
6) SEAL ALL JOINTS IN PIPE INSULATION AND APPLY PROTECTIVE COATING
7) GFI OUTLET REQUIRED OUTDOORS
NOTE:
NEW FURNACE REQUIRES A PERMIT AND INSPECTION. VENT IS NOT PROPERLY CONNECTED
07/27/2010 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WATER VENT NOT CONNECTED
2) GAS TURNED OFF, PROVIDE LISTED VENT CONNECTORS INSTALLED IN A WORKMANSHIP LIKE MANOR
3) NEW GAS WATER HEATER REQUIRES A NEW FLEX AND SEDIMENT TRAP
4) ALL PLUMBING PIPES, PARTS AND APPLIANCES SHALL BE INSTALLED PER THEIR LISTING REQUIREMENTS
5) INSPECTION STOPPED