Permit: T10CM01612

Parcel: 133263100


Addresses:

8343 E BALFOUR DR

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
10/21/2010 PLUMBING - INTERMEDIATE Approved
08/31/2010 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CORRECT DOOR LATCH
2) WOOD MAY NOT TOUCH GROUND
3) SEAL EXPOSED EDGES
4) NOTCH IN SIDE WALL
5) SECURE EACH JOINT OF VENT CONNECTOR WITH GALV SCREWS
6) INSTALL A SEDIMENT TRAP
7) CHECK OLD GAS VALVE WITH SOAP AND REPLACE IF NEEDED
8) PATCH HOLES IN ROOF WITH ROOFING TAR
9) SUPPORT TUBING ON ROOF
10) SCREW ALL SIDES OF ROOF FLASHINGS
11) SEAL AND COAT PIPE INSULATION
12) PROTECT INSULATION AND SECURE WITH CLAMPS AND FIT. (TRY TAPE OR HARD SLEEVE AROUND INSULATION AT CLAMPS) 6' MAX ON CENTER ON COPPER
13) CORRECT CONDUIT THAT WAS PUSHED DOWN AT PIPE CROSSING
07/20/2010 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/19/2010 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*