Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/09/2010 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/26/2010 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) TEMPERATURE AND PRESSURE RELIEF TO GRAVITY DRAIN TO DAYLIGHT OR BE INSTALLED PER PETITION OF APPEAL LEFT ON SITE WHICH WILL NEED TO BE SIGNED BY HOME OWNER
2) POTABLE PIPING TO BE SUPPORTED IN APPROVED METHOD AT EXISTING HEATER LOCATION
3) PROVIDE NON METALIC FLASHING AT POTABLE (COPPER PIPING TO THRU ROOF PENETRATION) TO AVOID DIS-SIMILAR CORROSION EFFECT
4) SOLAR LOOP PIPING TO BE SUPPORTED IN AN APPROVED METHOD NO J-HOOK DIRECTLY THRU ROOF MEMBRANE
5) SUPPORT ON ROOF TO BE MASTICED DOWN TO ROOF
6) VERIFY TEMPERATURE PRESSURE RELIEF IS FUNCTIONAL ON EXISTING WATER HEATER
7) INSULATION TO BE PROTECTED FROM DIRECT EXPOSURE TO SUN LIGHT PER MANUFACTURERS INSTALLATION INSTRUCTIONS
8) SUPPORT SOLAR LOOP TUBING AT CORRECT INTERVALS AT STORAGE TANK
9) 1/2" IP FLEX TO BE ROUTED TO PREVENT TRIPPING HAZARD GOING INTO DOOR AT GARAGE