Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/10/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXTEND TYPE B VENT TO 3' ABOVE COOLER 2) INSTALL ROOF FLASHINGS WITH TAR NOT SILICONE 3) FLASH OR SEAL WEATHER PROOF ENCLOSURE 4) COMPLETE PETITION OF APPEAL FOR T & P TERMINATION |
|
| 07/23/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INTERIOR WATER HEATER, T & P MAY NOT BE TRAPPED, FLEXES MAY NOT BE USED 2) BLOCK IRON NIPPLE NOT APPROVED FOR WATER 3) SECURE VENT CONNECTOR AND EXTEND TERMINATION 4) REPLACE OLD GAS FLEX 5) PROVIDE APPROVED WATER HEATER BASE 6) PROVIDE AN ENCLOSURE AT EXTERIOR WATER HEATER 7) INSULATE DOMESTIC PIPING PER INSTALLATION INSTRUCTIONS 8) PROVIDE BOTTLE OF ANTI FREEZE USED, MUST BE SAFE FOR POTABLE 9) FLASHING LISTED FOR COPPER 10) SUPPORT TUBING ABOVE ROOF ON BLOCKS 11) PATCH ALL HOLES IN ROOF |