Permit: T10CM01606

Parcel: 133262200


Addresses:

8314 E 7TH ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/22/2010 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/10/2010 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXTEND TYPE B VENT TO 3' ABOVE COOLER
2) INSTALL ROOF FLASHINGS WITH TAR NOT SILICONE
3) FLASH OR SEAL WEATHER PROOF ENCLOSURE
4) COMPLETE PETITION OF APPEAL FOR T & P TERMINATION
07/23/2010 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INTERIOR WATER HEATER, T & P MAY NOT BE TRAPPED, FLEXES MAY NOT BE USED
2) BLOCK IRON NIPPLE NOT APPROVED FOR WATER
3) SECURE VENT CONNECTOR AND EXTEND TERMINATION
4) REPLACE OLD GAS FLEX
5) PROVIDE APPROVED WATER HEATER BASE
6) PROVIDE AN ENCLOSURE AT EXTERIOR WATER HEATER
7) INSULATE DOMESTIC PIPING PER INSTALLATION INSTRUCTIONS
8) PROVIDE BOTTLE OF ANTI FREEZE USED, MUST BE SAFE FOR POTABLE
9) FLASHING LISTED FOR COPPER
10) SUPPORT TUBING ABOVE ROOF ON BLOCKS
11) PATCH ALL HOLES IN ROOF