Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
Permit Number - T10CM01591
Inspection Description - PLUMBING - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/16/2010 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/12/2010 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* TRAP ARM NOT CHANGE SIZE |
|
08/11/2010 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BREAKROOM SINK UNDER SLAB OK TO COVER 2) TRAP ARM MAY NOT CHANGE SIZE, TRAP AND TRAP ARM TO BE SAME SIZE-MAX LENGTH IN 1 1/2" TRAP ARM 3'-6" 3) USE APPROVED STRAPS |
|
07/30/2010 | PLUMBING - ABOVE CEILING | Partial Approval | 1) PROVIDE APPROVED SUPPORT AT 4' INTERVALS FOR HORIZONTAL ABS PIPING |