Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM01589
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | RED-LINE CHANGES FOR 1" C OVERHEAD TO CHILLERS OK. CONDUIT INSTALL OK CONDUIT TO ROOFTOP COOLING TOWERS OK. COOLING TOWERS REQUIRE DISCONNECTING MEANS WITHIN SIGHT OR A SUITABLE LOCKOUT DEVICE @ DISCONNECT ON 1ST FLOOR. |