Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T10CM01589

Parcel: 11716029A


Addresses:

103 E ALAMEDA ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/23/2011 ELECTRIC - INTERMEDIATE Partial Approval RED-LINE CHANGES FOR 1" C OVERHEAD TO CHILLERS OK. CONDUIT INSTALL OK

CONDUIT TO ROOFTOP COOLING TOWERS OK. COOLING TOWERS REQUIRE DISCONNECTING MEANS WITHIN SIGHT OR A SUITABLE LOCKOUT DEVICE @ DISCONNECT ON 1ST FLOOR.