Permit: T10CM01589

Parcel: 11716029A


Addresses:

103 E ALAMEDA ST


Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM01589

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
02/23/2011 ELECTRIC - INTERMEDIATE Partial Approval RED-LINE CHANGES FOR 1" C OVERHEAD TO CHILLERS OK. CONDUIT INSTALL OK

CONDUIT TO ROOFTOP COOLING TOWERS OK. COOLING TOWERS REQUIRE DISCONNECTING MEANS WITHIN SIGHT OR A SUITABLE LOCKOUT DEVICE @ DISCONNECT ON 1ST FLOOR.