Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2010 | MECHANICAL - ABOVE CEILING | Approved | ||
| 08/24/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OBD'S TO BE INSTALLED PRIOR TO FINAL 2) DUCT ABOVE CEILING OK TO COVER |
|
| 08/20/2010 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL BRANCH TAPS, DUCT AND FLEX PER DETAIL M1.0-2 2) PROVIDE O.B.D.'S PER PLANS 3) PROVIDE MINIMUM 2" BEADED COLLARS AT ALL FLEX DUCT CONNECTIONS PER MANUFACTURERS INSTALLATION INSTRUCTIONS 4) REMOVE ALL INSULATION AND DUCT JOINTS IN ORDER TO VERIFY DUCTS ARE SEALED ( I HAVE FOUND UN-SEALED JOINT) 5) PROVIDE DUCT HANGERS 48" ON CENTER PER PLANS 6) FLEX CONNECTOR NOT PROPERLY INSTALLED 7) COMPLETE VAV. INSTALLATION |